5.1.2 Functional description

The inputs NEW_PRES_MULTI and NEW_PRES_SINGLE are always read and
output to the TR_Pres_Multi and TR_Pres_Single outputs, irrespective of
the signal status of the other inputs. Once the preset block has been started via
the REQ input, the inputs NEW_PRES_MULTI and NEW_PRES_SINGLE may no
longer be changed.
The preset block is executed with the rising edge of the REQ input. The VALID
and
TR_Pres_Request and BUSY are set to 1.
The measuring system then executes the preset adjustment function. The time
for resetting the REQ input to 0 has no influence on the further execution of the
preset adjustment function.
When the preset adjustment function has been executed, the measuring system
sets the iParOK value of the measuring system F-IO data block and thus the
TR_IPAR_OK input to 1. With setting of the TR_IPAR_OK input, the
TR_Pres_Error input checks whether the preset adjustment function was
successfully executed. If the TR_Pres_Error input has the value 1, the ERROR
output is set to 1. Otherwise the VALID output is set to 1. With setting of the
TR_IPAR_OK input, the TR_IPAR_EN and TR_Pres_Request outputs are also
reset to 0.
When the TR_IPAR_EN output has been reset to 0, the measuring system resets
the iParOK value of the measuring system F-IO data block and thus the
TR_IPAR_OK input to 0.
With resetting of the TR_IPAR_OK input, the BUSY output is reset to 0.
Execution of the preset block is complete.
Printed in the Federal Republic of Germany
08/06/2021
ERROR
outputs
are
TR-ECE-TI-DGB-0292 v02
reset
to
0.
The
TR_IPAR_EN,
outputs
 TR-Electronic GmbH 2016, All Rights Reserved
Page 133 of 159