Operating the hand switch with 2 function buttons
Carrying out initialization
6.2 Carrying out initialization
Non-synchronous movement
Initialization run
Carrying out initialization
162
Carry out an initialization run in the following circumstances:
n
When commissioning the control unit for the first time
n
When the number of connected drives is changed
n
When resetting the control unit to factory settings
Connecting 2 - 8 control units in order to move drives synchro-
n
nously
n
Respective error message
Personnel:
Prerequisite:
All drives and control units are connected to each other.
n
1.
2.
3.
4.
5.
Control unit RK MultiControl II duo/RK MultiControl II quadro
NOTICE!
Material damage as a result of non-synchro-
nous movement of mechanically connected
drives!
An initialization run of the drives must be per-
formed before commissioning or installing them.
There is a risk of breakage during the initialization
run if drives are connected mechanically and
moved non-synchronously.
– Only carry out the initialization run without a
load and with extreme caution.
– Only move the drives by sight.
In order to be able to move the drives, the initiali-
zation run must be completed.
n
User
The system must be de-energised for at least
30 s.
Pull the mains plug and wait 30 s.
Press and hold the
Plug in the mains plug and wait approximately 5 s.
ð The LED display flashes red and green alternately.
Release the
buttons.
Press and hold the
moved into the lower final position.
Ä Page 217
buttons at the same time.
button until all drives have been
20.08.2021