14 Procedure for positioning, referencing and jogging
14.1 Set drive to "Positioning Mode"
To enable the drive to be positioned, referenced or jogged via Profibus, the drive must
first be put into Positioning Mode according to PROFIDRIVE V3.0. This can be done
by using the following procedure. Before, the mode of operation Positioning in the
parameter P930 must be preselected.
The order of the control commands (control word) and the interrogation of the
current status by means of the status word must be maintained, as otherwise the
command sent cannot be executed.
1.
Status word (ZSW, P968) returned after switch-on:
ZSW = 0000_0010_0100_0000
Bit6 (ZSW) = 1 => Switch on inhibit
Bit9 (ZSW) = 1 => Command required; the control system is requested to take over
command.
Status: SWITCH-ON INHIBIT
Action required: none
2.
Change from SWITCH ON INHIBIT to READY TO SWITCH ON
STW = 0000_0100_0000_0110
Bit1,2 (STW) = 1 => All "OFF2" and "OFF3" commands are canceled
Bit10 (STW) = 1 => Command assumed by control system; process data valid. Must
always be set for cyclical RT-communication via PROFINET.
Feedback:
ZSW =
0000_0010_0011_0001
Bit0 (ZSW) = 1 => Ready to switch on
Bit4, 5 (ZSW) = 1 => No "OFF2", "OFF3"
3.
Change from READY TO SWITCH ON to READY
STW =
0000_0100_0000_0111
Bit0 (STW) = 1 => Ready, voltage on converter
Feedback:
ZSW =
0000_0010_0011_0010
Bit1 (ZSW) = 1 => Ready
4.
Change from READY to OPERATION ENABLE
STW = 0000_0100_0000_1111
Bit0 (STW) = 1 => Enable electronics and pulses
Feedback:
ZSW = 0010_0010_0011_0100
Bit2 (ZSW) = 1 => Ready
Bit13 (ZSW) = 1 => encoTRive