Herunterladen Inhalt Inhalt Diese Seite drucken

Profinet Io Data Exchange; Figure 22: Device Communication - TR-Electronic MP-Series Benutzerhandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Commissioning

11.3 PROFINET IO Data exchange

PROFINET IO communication sequence:
According to his parameter setting, the IO-Controller establishes one or several
application relations to the IO-Devices. For this the IO-Controller is searching in the
network for parameterized names of the IO-Devices. Then the IO-Controller
distributes an IP-Address to the located devices. In this case the service DCP
"Discovery and Control Program" is used. In the following start-up the IO-Controller
transmits the desired capabilities (modules/submodules) and all parameters for the
parameterized IO-Devices. The cyclical IO-Data, alarms, acyclic services and
multicast communications are defined.
With PROFINET IO the transmission rate of the individual cyclic data can be adjusted
by a reduction factor. After the parameter setting the IO-Data of the IO-Device are
transferred according to unique request of the IO-Controller with a constant clock.
Cyclic data are not acknowledged. Alarms must be always acknowledged. Acyclic
data are acknowledged also.
For protection against parameterization errors the required capability and the actual
capability is compared in relation to the Device type, the Order-No. and the Input- and
Output data.
With
a successful system boot the IO-Devices start automatically with the data
transmission. In case of PROFINET IO a communication relation always follows the
provider consumer model. With cyclical transmission of the IO-Data, the IO-Device
corresponds to the provider of the data, the IO-Controller (e.g. a PLC) corresponds to
the consumer. The transferred data always contains a status (good or bad).

Figure 22: Device communication

AR:
Application relation between IO-Controller and assigned IO-Devices
CR:
Communication relations for configuration, process data and alarms
 TR-Electronic GmbH 2008, All Rights Reserved
Page 218 of 252
TR - EMO - BA - DGB - 0019 - 08
Printed in the Federal Republic of Germany
06/06/2019