10.4.9
Status area and status displays
Settings
1.1
Set auto control
Settings assistant, setpoints, options
Manual operation
Manual override
Double pump operation
Set double pump
External interfaces
Analogue, digital, SSM, SBM
Fig. 36: Main menu status display
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
The status area is located on the left side above the main menu area
Overriding
screen" [} 167] figure and table).
auto control via
manual intervention.
If a status is active, it is possible to display and select status menu items in the main menu.
Turn the operating button to the status area to show the active status.
If an active process (e.g. software update) is quit or discarded, the status display is hidden
again.
There are three different classes of status displays:
1.
Display process:
On-going processes have been highlighted in blue.
Processes mean pump operation may deviate from the adjusted control.
Example: software update.
2.
Display warning:
Warning messages have been highlighted in yellow.
The pump functions are restricted if a warning has been output (see "Warning mes-
sages" [} 219] section).
Example: Cable break detection on analogue input.
3.
Display error:
Error messages have been highlighted in red.
The pump stops operation if an error has occurred. (see "Error messages" [} 218] sec-
tion).
Example: ambient temperature too high.
Further status displays, if available, can be displayed by turning the operating button to the
corresponding symbol.
Symbol
Table 18: Potential data displayed in the status area
Additional settings can be made in the "Context" menu, if necessary. For this purpose, press
the Context button
Press the Back button
Meaning
Error message
Pump stopped!
Warning message
Pump operation restricted!
Communication status – a CIF module has been installed and is active.
Pump in control mode, monitoring and control by building automation
available.
Software update started – transfer and verification
Pump continues to run in control mode until the update bundle has
been fully transferred and verified.
.
to return to the main menu.
NOTICE
A set control mode is interrupted when a process is running. The pump
starts to run in the set control mode once the process is ended.
NOTICE
Repeatedly pressing or pressing and holding the Back button after an error
message has occurred will open the "Error" status display and not take you
back to the main menu.
The status area is highlighted in red.
en