Optional cable break detection
Analogue input (AI2)
Switched off
Switched on
Fig. 76: Optional cable break detection
Optional cable break detection
Analogue input (AI2)
Switched off
Switched on
Limit value
Fig. 77: Cable break limit value
ON/OFF through analogue signal
Analogue input (AI2)
Switched off
Switched on
Fig. 78: On/off through analogue signal
Limit values for ON/OFF
Analogue input (AI2)
Limit value OFF
Switched on
Limit value ON
Fig. 79: Limit values for ON/OFF control
through analogue signal
Minimum signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Fig. 80: Minimum signal/value assignment
202
Select "Switched off" to switch off cable break detection.
The behaviour of the analogue input is in line with the threshold of the signal standard as-
Signal strength below
the set limit value
is interpreted as
signment.
a cable break.
Select "Switched on" to activate cable break detection only below an adjustable limit value.
Define limit value for cable break by turning the operating button and confirm by pressing it.
Signal strength below
In the next step define whether
the set limit value
is interpreted as
a cable break.
the analogue signal only changes the setpoint
and the pump is additionally switched off through the analogue signal.
A setpoint change can be done through analogue signals without switching on and off the
pump through the signals. In this case, "Switched off" is selected.
If the "On/off by analogue signal" function is switched on, the limit values must be defined
for the switch on/off.
Subsequently assign the MIN signal/value and MAX signal/value.
For the transfer of analogue signal values to setpoints, only the transfer ramp is now defined.
For this purpose, the minimum and maximum support points of the characteristic curve are
The analogue signal
changes the setpoint and
switches the pump ON
specified and the respective setpoints are amended (MIN signal/value assignment and MAX
or OFF
via a limit value.
signal/value assignment).
The analogue signal
changes the setpoint and
switches the pump ON
or OFF
via these limit values.
The value for the minimum signal describes the lower signal value of the transmission ramp
with an associated value of 0 %. In this example, the lower signal value is 3 V.
Set minimum point
of setpoint pump curve of
delivery head for Δp-v
.