Control mode
Sec. feed temperature...
Return ΔT
Multi-Flow Adaptation
Volume flow Q-c
Hydraulic shunt
Fig. 55: Example "Multi-Flow Adaptation"
control mode
Set control mode
Setting assistant
Current: hydraulic shunt – Multi...
Feeder pump correction factor
Current: 50 %
Selection of secondary pumps
Number of secondary pumps: 0
Multi-Flow Adaptation Overview
Number of consumer circuit pumps: 0
Fig. 56: Set control mode
Set control mode
Setting assistant
Current: hydraulic shunt – Multi...
feeder pump correction factor
Current: 50 %
Selection of secondary pumps
Number of secondary pumps: 0
Multi-Flow Adaptation Overview
Number of consumer circuit pumps: 0
Fig. 57: Setting assistant – Selection of sec-
ondary pumps
MFA consumer circuit pump selection
End selection
PartnerName_1001
PartnerName_1002
PartnerName_1003
PartnerName_1004
PartnerName_1005
Fig. 58: Selection of secondary pumps for
Multi-Flow Adaptation
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Control mode
‣ Volume flow Q-const
Table 28: Selection of control mode for Hydraulic shunt system type in the heating applica-
tion
Example: "Multi-Flow Adaptation" control mode
Select the "Multi-Flow Adaptation" control mode by turning the operating button and press
to confirm.
Feeder pump
determines the
required
volume flow to
When the selection is confirmed, "Setting assistant" will be displayed in the menu.
supply the
hydraulic shunt
from measured values of the
allocated
secondary pumps.
Settings help
Additional settings must be made.
Select a control mode via the
application and
system type.
All control modes
are also available to be selected
directly.
Select secondary pumps that have to be supplied downstream of the hydraulic shunt and
connect them to Wilo Net.
Selecting of
secondary pumps which are used
for measuring the
volume flow in Multi-
Select "Selection of secondary pumps" by turning the operating button and press to confirm.
Flow Adaptation
.
Each partner pump has to be selected as secondary pump from the pumps detected by Wilo
Net.
Select the partner pump by turning the operating button and press to confirm.
When pressed, the white tick appears on the selected pump.
This pump signals
the focus.
The secondary pump indicates for its part on the display that it has been selected.
Type: 25/1-1004
Item no.: 12 1004
NodeID: 954
All other secondary pumps are selected in the same way. Then press the Back button to go
Serial no.:
341004
back to the "Set control mode" menu.
When secondary pumps are installed in a circuit with a mixer, the mixed volume flow can be
taken into account. For this purpose, select and activate the additional control function
Selection menu
Multi-Flow Adaptation mixer.
en
185