Mains connection

156
Name
Assignment
Analogue IN (AI3)
+ 24 V (terminal: 6)
(Fig. 20)
+ In 3 → (terminal: 7)
- GND (terminal: 8)
Analogue IN (AI4)
+ In 4 → (terminal: 9)
(Fig. 20)
- GND (terminal: 10)
Digital IN (DI1)
DI1 → (terminal: 11)
(Fig. 20)
+ 24 V (terminal: 12)
Digital IN (DI2)
DI2 → (terminal: 13)
(Fig. 20)
+ 24 V (terminal: 14)
Wilo Net
↔ H (terminal: 15)
(Fig. 20)
↔ L (terminal: 16)
GND H/L (terminal: 17)
SSM
COM (terminal: 18)
(Fig. 23)
← NO (terminal: 19)
← NC (terminal: 20)
SBM
COM (terminal: 21)
(Fig. 23)
← NO (terminal: 22)
← NC (terminal: 23)
Mains connection
Table 11: Terminal assignment
NOTICE
Nationally applicable guidelines, standards and regulations as well as the
requirements of local energy supply companies must be observed!
NOTICE
Tightening torques for the terminal screws, see "Tightening torques"
[} 145] table. Only use a calibrated torque wrench!
1.
Observe the current type and voltage on the rating plate.
2.
Establish the electrical connection via a fixed connection cable equipped with a con-
nector device or an all-pole switch with a contact opening width of at least 3 mm.
3.
To protect against leakage and for strain relief to the threaded cable gland, use a con-
nection cable with sufficient outer diameter.
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Notice
Type of signal:
• 0 ... 10 V
• 2 ... 10 V
• 0 ... 20 mA
• 4 ... 20 mA
• PT1000
Electric strength:
30 V DC / 24 V AC
Power supply:
24 V DC: at maximum 50 mA
Digital inputs for potential-free
contacts:
• Maximum voltage:
< 30 V DC / 24 V AC
• Maximum loop current: < 5 mA
• Operating voltage: 24 V DC
• Operating loop current:  2 mA per
input
Potential-free changeover contact
Contact load:
• Permitted minimum: SELV
12 V AC / DC, 10 mA
• Permitted maximum: 250 V AC,
1 A, 30 V DC, 1 A
Potential-free changeover contact
Contact load:
• Permitted minimum: SELV
12 V AC / DC, 10 mA
• Permitted maximum: 250 V AC,
1 A, 30 V DC, 1 A