Operating Data/Statistics - Wilo -Stratos GIGA2.0-I Einbau- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Wilo-Stratos GIGA2.0-I:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

en
Display of heating quantity
Total heating quantity:
0.00 MWh
Heating quantity:
0.00 MWh
since 18733
days 9 h 54 min
Actual heating capacity:
Actual feed temperature:
Actual return temperature:
Actual volume flow:
Fig. 92: Display of heating quantity
15.3

Operating data/statistics

212
Information about the
total heating quantity,
the heating quantity since
the last counter
reset and the
measured values for
calculating the
current heating capacity.
Set heating quantity to
"0"
In the "Diagnostics and measured values" menu
1.
"Operating data, statistics".
The following operating data, measurement data and statistical data are displayed:
Hydraulic operating data
Actual delivery head
Actual volume flow
Actual fluid temperature (if a temperature sensor is connected and configured)
Electrical operating data
Mains voltage
Power consumption
Total energy absorbed
Operating hours
Measured heat quantity
Total heating quantity
Heat quantity since the last time the counter was re-set
Actual heat output
Actual feed temperature
Actual return temperature
Actual volume flow
Measured cooling quantity
Total cooling quantity
Cooling quantity since the last time the counter was re-set
Actual cooling output
Actual feed temperature
Actual return temperature
Actual volume flow
Accuracy of the displayed and recorded operating data
Volume flow
The volume flow is determined with the help of the connected differential pressure sensor.
The accuracy of the volume flow specification with pure water is approx. +/- 5 % of the
duty point.
If a water-glycol mixture is used, the accuracy is in the range of +/-10 % ... 50 % depend-
ing on the mixing ratio.
Temperature
External sensors such as PT1000 must always be connected for temperature measurement.
Accuracy information is not available here as it depends on the following factors:
how and where temperature sensors are installed on the piping;
which accuracy class of the sensor was selected;
length of the sensor cable.
The accuracy within the Stratos GIGA2.0 is up to +/- 2 K depending on the temperature
value.
Heating/cooling quantity measurement
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
NOTICE
The energy measurement for heating or cooling can be conducted without
an additional energy meter. The measurement can be used for the internal
distribution of heating and cooling costs or for system monitoring. As the
heating and cooling quantity measurement is not calibrated, it cannot be
used as the basis for billing.
NOTICE
For constant recording of the heating/cooling quantity without interrupt-
ing data recording, the pump must only be switched on/off via a digital in-
put with EXT. OFF. There is no data recording when the mains voltage is
switched off.