CAUTION
A dry run leads to bearing damage!
Ensure that a dry run of the pump is not possible!
8.1

Filling and venting

Fill and vent the system correctly. The pump rotor chamber normally vents automatically after a short time in
operation.
NOTICE
Incomplete venting will lead to noises in the pump.
8.2

Setting the control mode

8.2.1 Pumps with operating button
(Fig. I a):
The control mode is selected with the operating button.
The following settings can be configured:
Constant differential pressure (Δp-c) setting range
Fig. I a, Item 9: The control mode Δp-c is active.
The number indicates the delivery head in metres of the water
column.
Variable differential pressure (Δp-v) setting range
Fig. I a, Item 10: The control mode Δp-v is active.
The digit indicates the delivery head in metres of the water column
at nominal flow rate.
Setting range ext. In
Fig. I a, Item 8: The external control is active. The control mode de-
pends on the technical version of the product. (See section
"Equipment variants")
The following settings are possible:
Setpoint adjustment via analogue input 0 ... 10 V.
Setpoint adjustment via pulse-width modulation (PWM).
Setpoint adjustment at constant speed (not externally controlled).
Factory setting
The pump is supplied with the setting mode "ext. In" as standard.
8.2.2 Pumps without operating button
(Fig. I b):
The pump automatically follows its external control function. The control mode depends on the technical
version of the product. (See section "Equipment variants")
Installation and operating instructions • Wilo-Stratos PARA-C/-CZ • Ed.01/2023-04