12.2

Twin-head pump behaviour

12.3
Settings menu – Twin-head pump
operation
Settings
Set control mode
Setting assistant, setpoints, options
Manual operation
Manual override
Twin-head pump operation
Set twin-head pump
External interfaces
Analogue, digital, SSM, SBM ...
Fig. 63: Menu Twin-head pump operation
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
The control of both pumps starts from the main pump to which the differential pressure
sensor is connected.
In case of breakdown/fault/communication interruption, the main pump alone takes over
complete operation. The main pump runs as a single pump according to the set operating
modes of the twin-head pump.
The standby pump, which receives no data from the differential pressure sensor, runs in the
following cases at an adjustable constant emergency operation speed.
The main pump to which the differential pressure sensor is connected fails.
The communication between the main pump and the standby pump is interrupted.
The standby pump starts immediately after detecting a fault.
In the "Twin-head pump operation" menu, a twin-head pump connection can be established
or disconnected and the twin-head pump function can also be adjusted.
Settings of
twin-head pump operation,
addressing of
twin-head pump partner,
mode etc.
In the "Settings" menu
1.
Select twin-head pump operation.
Menu "Twin-head pump function"
When a twin-head pump connection is established, the "Twin-head pump function" menu is
used to switch between
Main/standby operation and
Efficiency-optimised peak-load operation (parallel operation)
.
Menu "Pump cycling interval"
If a twin-head pump connection is established, the time interval can be set in the "Pump
cycling interval" menu. Time interval: between 1 h and 36 h, factory setting: 24 h.
An immediate pump cycling can be triggered via the menu item "manual pump cycling".
Manual pump cycling can always be carried out regardless of the configuration of the time-
based pump cycling function.
Menu "Connecting twin-head pump"
If twin-head pump connection is not yet established, in the "Settings" menu 
1.
"Twin-head pump operation"
2.
"Connecting twin-head pump".
When the Wilo Net connection is established (see "Wilo Net [} 205]" section), a list of avail-
able and appropriate twin-head pump partners will appear under "Connecting twin-head
NOTICE
For the installation of two single pumps to form a twin-head pump, see
sections "Twin-head pump installation/Y-pipe installation" [} 149],
"Electrical connection" [} 150] and "Application and function of the Wilo
Net interface" [} 205].
, select
NOTICE
When switching between main/standby operation and parallel operation,
different parameters of the pump are fundamentally changed. The pump is
then started automatically.
NOTICE
The pump from which the twin-head pump connection is started is the
main pump. Always select the pump to which the differential pressure
sensor is connected as the main pump.