12.2
Twin-head pump behaviour
12.3
Settings menu – Twin-head pump
operation
Settings
Set control mode
Setting assistant, setpoints, options
Manual operation
Manual override
Twin-head pump operation
Set twin-head pump
External interfaces
Analogue, digital, SSM, SBM ...
Fig. 63: Menu Twin-head pump operation
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
The control of both pumps starts from the main pump to which the differential pressure
sensor is connected.
In case of breakdown/fault/communication interruption, the main pump alone takes over
complete operation. The main pump runs as a single pump according to the set operating
modes of the twin-head pump.
The standby pump, which receives no data from the differential pressure sensor, runs in the
following cases at an adjustable constant emergency operation speed.
•
The main pump to which the differential pressure sensor is connected fails.
•
The communication between the main pump and the standby pump is interrupted.
The standby pump starts immediately after detecting a fault.
In the "Twin-head pump operation" menu, a twin-head pump connection can be established
or disconnected and the twin-head pump function can also be adjusted.
Settings of
twin-head pump operation,
addressing of
twin-head pump partner,
mode etc.
In the "Settings" menu
1.
Select twin-head pump operation.
Menu "Twin-head pump function"
When a twin-head pump connection is established, the "Twin-head pump function" menu is
used to switch between
•
Main/standby operation and
•
Efficiency-optimised peak-load operation (parallel operation)
.
Menu "Pump cycling interval"
If a twin-head pump connection is established, the time interval can be set in the "Pump
cycling interval" menu. Time interval: between 1 h and 36 h, factory setting: 24 h.
An immediate pump cycling can be triggered via the menu item "manual pump cycling".
Manual pump cycling can always be carried out regardless of the configuration of the time-
based pump cycling function.
Menu "Connecting twin-head pump"
If twin-head pump connection is not yet established, in the "Settings" menu
1.
"Twin-head pump operation"
2.
"Connecting twin-head pump".
When the Wilo Net connection is established (see "Wilo Net [} 205]" section), a list of avail-
able and appropriate twin-head pump partners will appear under "Connecting twin-head
NOTICE
For the installation of two single pumps to form a twin-head pump, see
sections "Twin-head pump installation/Y-pipe installation" [} 149],
"Electrical connection" [} 150] and "Application and function of the Wilo
Net interface" [} 205].
, select
NOTICE
When switching between main/standby operation and parallel operation,
different parameters of the pump are fundamentally changed. The pump is
then started automatically.
NOTICE
The pump from which the twin-head pump connection is started is the
main pump. Always select the pump to which the differential pressure
sensor is connected as the main pump.
en
, select
189