10.4.2
Settings on pump
Set auto control
Settings assistant
Current: Fan heater – Dynamic Adapt ...
Emergency operation speed
Constant speed: 2000/Min
Pump ON/OFF
Current: Motor on
Fig. 29: Green focus: Navigation in menu
Control mode
Differential pressure Δp-v
Dynamic Adapt plus
Hall temperature T-const
Fig. 30: Yellow focus: Adjusting the settings
10.4.3

Initial settings menu

Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Approximate calculation of Q
Q
= 10 % x Q
min
Carry out settings by turning and pressing the operating button. Turn the operating button
to the left or right to browse the menus or configure settings. A green focus indicates navig-
Select a control mode via the
application and
system type.
ation in the menu. A yellow focus indicates a configuration of settings.
All control modes
are also available to be selected
directly.
Green focus: Navigation in menu.
Yellow focus: Change settings.
Turn
Press
Press the "Back" button
the focus back to the previous focus. Consequently, the focus moves one level further up in
the structure or to a previous setting.
Pressing the Back button
Pump adjusts its
performance to the
ing the changed value returns the focus to the previous focus. The adjusted value will be dis-
variable demand of
the radiators.
Input of the delivery head
carded. The previous value remains unchanged.
(design point)
required.
If the Back button
pump can be operated from the main menu.
Settings help
The settings menu will appear in the display during initial commissioning of the pump.
CAUTION
Risk of material damage!
An inadequate volume flow can lead to damage on the mechanical seal;
the minimum volume flow depends on the speed of the pump.
• Make sure that the volume flow does not fall below the minimum
value Q
.
min
:
min
 x actual speed / max. speed
max pump
 : menu selection and parameter setting.
 : Activation of menus or confirming settings.
("Description of operating elements" [} 164] table) to change
after having changed a setting (yellow focus) without confirm-
is pressed for more than 2 seconds, the Home screen opens and the
NOTICE
The changed settings are stored in the memory with a delay of 10 seconds.
If the power supply is interrupted during this time, the settings are lost.
NOTICE
If there are no warning or error messages, the display on the electronic
module will switch off 2 minutes after the last time it was operated.
• If the operating button is pressed or turned again within 7 minutes, the
previously exited menu will appear. You can continue to configure set-
tings.
• If the operating button is not pressed or turned for more than 7 minutes,
any unconfirmed settings will be lost. Pressing the button again opens the
Home screen on the display and the pump can be operated from the main
menu.
NOTICE
The factory setting for variant ... R1 (without differential pressure sensor
in delivery status) is the basic control mode "Constant speed". The fact-
ory setting mentioned below refers to the variant with a differential
pressure sensor fitted in the factory.
en
165