14.5

Device information

14.6

Pump kick

Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
NOTICE
You can also lock the keys using the digital inputs DI 1 and DI 2 (see sec-
tion "Application and function of the digital control inputs DI1 and DI2"
[} 195]).
If the key lock was activated through digital inputs DI1 or DI2, the deac-
tivation can be done only through the digital inputs! A button combina-
tion is not possible!
The home screen and warning as well as error messages are also displayed when the key
lock is active so you can monitor the pump status.
A lock symbol
on the home screen indicates an activated key lock.
Under "Settings"
1.
"Device settings"
2.
"Device information"
you can read information about product names, the product and serial number as well
as software and hardware version.
In order to prevent blocking of the pump, a pump kick is set on the pump. After a set time
interval, the pump starts and switches off after a short time.
Prerequisite:
for the pump kick function, the mains voltage must not be interrupted.
CAUTION
Blockage of the pump due to long downtimes!
Long downtimes may lead to blockage of the pump. Do not deactivate
pump kick!
Pumps switched off through remote operation, bus command, control input External OFF or
0 ... 10 V signal run for a short time. This prevents blockage after long downtimes.
In the "Settings" menu 
, select
1.
"Device settings"
2.
"Pump kick"
The time interval for the pump kick can be set between 2 and 72 hours (factory setting:
24 h).
The pump kick can be switched on and off.
NOTICE
When it is planned to switch off the mains voltage for a longer period of
time, the pump kick must be performed using an external control by
switching on the mains voltage briefly.
For this purpose, the pump must be switched on by the controller before
the power supply is interrupted.