Commissioning
8.1

Filling and venting

Fill and vent the system correctly. The pump rotor chamber normally vents automati-
cally after a short time in operation.
NOTICE
Incomplete venting will lead to noises being produced in the pump.
Pump venting function
See section "Information about the product" to find out if your pump type is
equipped with this function.
If the pump does not vent automatically, a pump venting function can be started.
ƒ
ƒ
The pump venting function vents the pump automatically.
The heating system is not vented.
The maximum duration is 10 minutes.
The following animation appears during this process:
NOTICE
After the venting, the pump activates the previously selected control mode.
8.2

Setting the control mode

Wilo-Para MAXO ... F01/F02 only:
Selecting the control mode:
ƒ
Change control mode:
ƒ
Repeat the process until the LED of the desired control mode lights up.
88
Activate pump venting function via the operating button: Press and hold for 4
seconds until all the LEDs flash 2 times. Then release the button.
The function can be stopped at any moment in the same manner as it is activ-
ated.
Display of active control mode by LEDs (Fig. I, Item 9).
Press and hold the operating button for 2 seconds until the LED of the next con-
trol mode lights up, then release it.
WILO SE 2022-04