Herunterladen Inhalt Inhalt Diese Seite drucken

Wilo -Stratos GIGA2.0-I Einbau- Und Betriebsanleitung Seite 146

Vorschau ausblenden Andere Handbücher für Wilo-Stratos GIGA2.0-I:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

en
146
WARNING
Risk of personal injury and property damage due to improper
handling!
• Never set up the pump unit on unfortified surfaces or surfaces that
cannot bear loads.
• Flush the pipe system if required. Dirt can cause the pump to fail.
• Install only after completion of all welding and soldering work and
after the pipe system has been flushed, if required.
• Observe the minimum axial distance of 400 mm between a wall and
the fan cover of the motor.
• Ensure free air access to the heat sink of the electronic module.
The pumps must be protected from the weather and installed in a frost/dust-free, well-
ventilated environment that is not potentially explosive. Observe the specifications in
the section "Intended use"!
Mount the pump in a readily accessible place. This makes it easier to complete inspec-
tions, maintenance (e.g. mechanical seal change) or replacement in the future.
Install a device for attaching hoisting gear above the set-up site of large pumps. Total
weight of the pump: see catalogue or data sheet.
WARNING
Personal injury and property damage due to improper handling!
Transport lugs mounted on the motor housing can tear out if the load is
too heavy. This can lead to serious injuries and damage to the product!
• Never transport the entire pump with the transport lugs attached to
the motor housing.
• Never use the transport lugs attached to the motor housing to separ-
ate or pull out the motor impeller unit.
Only lift the pump with approved lifting gear (e.g. block and tackle, crane). See also
"Transport and storage" [} 136] section.
Transport lugs mounted on the motor housing are only permitted for transporting the
motor!
NOTICE
Simplify subsequent work on the unit!
• To ensure the entire unit does not have to be emptied, install shut-off
valves upstream and downstream of the pump.
CAUTION
Material damage due to turbine and generator operation!
Flowing through the pump in the direction of flow or against the direc-
tion of flow can cause irreparable damage to the drive.
Install a swing check valve on the discharge side of each pump!