Configuration Warnings - Wilo -Stratos GIGA2.0-I Einbau- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Wilo-Stratos GIGA2.0-I:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

en
Code
Warning
Additional information about causes and remedy:
Twin-head pump function is only possible with two compatible pumps of the same type.
584
Internal fault in display and control unit.
There is an automatic restart of the display.
Additional information about causes and remedies:
The basic pump functions are not impacted by this fault.
586
Overvoltage
Additional information about causes and remedy:
The pump is running. If the voltage continues to increase, the pump is shut down.
Excessive voltages can damage the pump.
587
Battery weak.
Additional information about causes and remedies:
If the battery power is high enough, the time information, e.g. in heat measurement and statistics, is displayed correctly.
If the battery power is too low, it may not be possible to maintain time recording.
This does not impair the pump function
588
Electronic fan blocked, defective or not
connected.
Additional information about causes and remedies:
The pump continues to run but may no longer be able to provide full power.
589
Battery empty
Additional information about causes and remedies:
The pump's time recording might be faulty.
The time data e.g. in heat/cooling quantity measurement, restore points and statistical data may not be correct.
The basic pump function is not impaired.
1)
590
MFA
partner type is not appropriate.
Additional information about causes and remedy:
A maximum replacement flow is provided for the Multi-Flow Adaptation partner.
Check the partners highlighted with (!) in the MFA
Table 57: Warning messages
18.5

Configuration warnings

Code
Fault
601
Setpoint source not suitably con-
figured.
The setpoint source is not correctly configured. In the context menu there is a link for configuring the setpoint
source.
602
Setpoint source not available.
The setpoint source or the CIF module is not correctly configured. In the context menu there are links for configura-
tion.
603
Sensor source not suitably con-
figured.
The sensor source is not correctly
configured. In the context menu
there is a link for configuring the
sensor source.
222
Cause
Power supply is too high.
Battery power too low
Electronic fan does not work.
Battery discharged
1)
A MFA
partner does not have the
appropriate type.
1)
overview of the context menu.
1)
MFA = Multi-Flow Adaptation
2)
BMS = Building Management System
Configuration warnings occur if an incomplete or contradictory configuration has been
made.
Example:
The "Hall temperature control" function requires a temperature sensor. The corresponding
source is not specified or not correctly configured.
Cause
Setpoint is not connected to correct
source. Input not suitably configured.
Setpoint not connected to existing
CIF module.
Sensor 1 is not connected to correct
source. Input not suitably configured.
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Remedy
Contact service.
Replace display and control unit.
Check power supply.
Replace battery.
Check the fan cable.
The battery must be replaced
promptly to avoid possible further
deviations in time recording.
Check type and software of the
partner pump.
Remedy
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
Configure source.
Select other source.