Select type of use
Analogue input (AI3)
Not configured
Setpoint sensor
Differential pressure sensor
Temperature sensor
External sensor
Fig. 83: Settings dialogue actual value sensor
Signal type: analogue input (AI3)
For temperature sensor
PT1000
0 – 10 V
2 – 10 V
0 – 20 mA
4 – 20 mA
Fig. 84: Signal type
Minimum signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Fig. 85: Minimum signal/value assignment,
actual value sensor
Max. signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Fig. 86: Maximum signal/value assignment,
actual value sensor
204
In the "Settings" menu 
Use analogue input as
actual value input for
temperature sensor
1.
"External interfaces"
, e.g. for
temperature T-c.
2.
"Function analogue input AI1" ...  "Function analogue input AI4"
3.
"Set analogue input".
First select type of use:
Select one of the types of use "Differential pressure sensor", "Temperature sensor" or "Ex-
ternal sensor" as one of the usage types.
Select the "Signal type" after selecting the actual value sensor:
Set analogue input to
When selecting the signal type "PT1000", all settings for the sensor input are completed and
signal type 0 ... 20 mA
.
all other signal types require additional settings.
For the transfer of analogue signal values to actual values, only the transfer ramp is now
defined. For this purpose, the minimum and maximum support point of the characteristic
curve is specified and the respective actual values are amended (MIN signal/value assignment
and MAX signal/value assignment).
The value for the minimum signal describes the lower signal value of the transmission ramp
with an associated value of 0 %. This is the equivalent of 0.0 mA for -10 °C in this example.
Set minimum point
of actual value
pump curve for
temperature sensor.
Data input is complete once the minimum and maximum characteristic curve support points
have been entered.
The value for the maximum signal describes the upper signal value of the transmission ramp
with an associated value of 100 %. This is the equivalent of 20.0 mA for 120 °C in this ex-
Set maximum point
ample.
of actual value
pump curve for
temperature sensor.
In the "Settings" menu 
1.
"External interfaces"
2.
"Function analogue input AI1" ...  "Function analogue input AI4"
3.
"Temperature correction" and set correction value (offset).
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
, select
NOTICE
If another usage type has been set to "Not configured" in the "Select type
of use" menu, check whether the analogue input is already used for an-
other type of use.
If necessary, select a different source.
NOTICE
If the analogue input is configured to the signal type PT1000 for a temper-
ature sensor, a "temperature correction value" can be set to compensate
for the electrical resistance if the sensor cable is longer than 3 m.
NOTICE
If the signal type PT1000 has been selected, it's possible to set a temper-
ature correction value for the measured temperature. With this the elec-
trical resistance of a long sensor cable can be compensated.
, select