Application and function of the
Wilo Net interface
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
NOTICE
Optionally specify the position of the sensor for better understanding of
the connected sensor's function.
This configured position does not influence the function or sensor use.
In the "Settings" menu 
, select
1.
"External interfaces"
2.
"Function analogue input AI1" ...  "Function analogue input AI4"
3.
"Select the sensor position".
The following positions are available:
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
BMS (Building management systems)
Feed
Return
Primary circuit 1
Primary circuit 2
Secondary circuit 1
Secondary circuit 2
Accumulator
Hall
Wilo Net is a bus system which enables up to 21 Wilo products (participants) to communic-
ate with one another. The Wilo-Smart Gateway is one of these participants.
Application for:
twin-head pumps consisting of two participants
Multi-Flow Adaptation (feeder pump connected to secondary pumps)
remote access via Wilo-Smart Gateway
Bus topology:
The bus topology consists of multiple participants (pumps and Wilo-Smart Gateway), which
are switched on in sequence. The participants are connected via a shared cable.
The bus must be terminated at both ends of the cable. This is done for the two external
pumps in the pump menu. All other subscribers should not have activated termination.
All bus subscribers must be assigned an individual address (Wilo Net ID).
This address is set in the pump menu of the respective pump.
To terminate the pumps:
In the "Settings" menu 
, select
1.
"External interfaces"
2.
"Wilo Net setting"
3.
"Wilo Net termination".
Possible selection:
Wilo Net termination
Switched on
Switched off
After termination is done, an individual Wilo Net address is assigned to the pumps:
In the "Settings" menu 
, select
1.
"External interfaces"
2.
"Wilo Net setting"
Description
Terminating resistor of the pump is switched on.
If the pump is connected at the end of the electrical bus line,
"Switched on" must be selected.
The pump's terminating resistor is switched off.
If the pump is NOT connected at the end of the electrical bus
line, "Switched off" must be selected.