Fault
604
Same sensor source not possible.
The sensor sources are not correctly configured. In the context menu there is a link for configuring the sensor
sources.
606
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.
607
Sensor source not suitably con-
figured.
The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.
609
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.
610
Sensor source not suitably con-
figured.
The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.
611
Same sensor source not possible.
The sensor sources are not correctly configured. In the context menu there is a link for configuring the sensor
sources.
614
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.
615
Sensor source not suitably con-
figured.
The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.
618
Sensor source not available.
The sensor source or the CIF module
is not correctly configured. In the
context menu there are links for con-
figuration.
619
Sensor source not suitably con-
figured.
The sensor source is not correctly configured. In the context menu there is a link for configuring the sensor source.
621
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are links for configuration.
641
Setpoint source not suitably con-
figured.
The setpoint source for the cooling function is not correctly configured. In the context menu there is a link for con-
figuring the setpoint source.
642
Setpoint source not available.
The setpoint source for the cooling function or the CIF module is not correctly configured. In the context menu there
are links for configuration.
643
Sensor source not suitably con-
figured.
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Cause
Sensor sources are configured to the
same source.
Sensor value 1 is not connected to
existing CIF module.
Sensor 2 is not connected to correct
source. Input not suitably configured.
Sensor value 2 is not connected to
existing CIF module.
Feed temperature sensor is not con-
nected to correct source. Input not
suitably configured.
Sensor sources for heat meter con-
figured for the same source.
Feed temperature is not connected to
existing CIF module.
Return temperature sensor is not
connected to correct source. Input
not suitably configured.
Return temperature is not connected
to existing CIF module.
Temperature sensor for "Heating/
cooling switchover" is not connected
to the correct source. Input not suit-
ably configured.
Temperature value for "Heating/cool-
ing switchover" is not connected to
existing CIF module.
Setpoint is not connected to correct
source. Input not suitably configured.
Setpoint not connected to existing
CIF module.
Sensor 1 is not connected to correct
source. Input not suitably configured.
Remedy
Configure a sensor source to another
source.
Insert CIF module.
Activate CIF module.
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
Configure source to "temperature
sensor" usage type or select another
source.
Configure one of the sensor sources
for the heat meter to another source.
Insert CIF module.
Activate CIF module.
Configure source to "temperature
sensor" usage type or select another
source.
Insert CIF module.
Activate CIF module.
Configure source to "temperature
sensor" usage type or select another
source.
Insert CIF module.
Activate CIF module.
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
Configure source.
Select other source.