9. HEATING
Adjustment
Description
channel
TFlowmin
Minimum flow temperature
TOutdoor 1
Lower outdoor temperature
TFlow 1
Lower set flow temperature
TOutdoor 2
Upper outdoor temperature
TFlow 2
Upper set flow temperature
TFlowmin
Minimum flow temperature
TFlowmax
Maximum flow temperature
Output
Output selection
Mode
Cooling mode
Sensor
Switch input selection
Inverted
Inverted switching option
TDay off
Outdoor temperature cooling
Timer
Timer function cooling
tOn
Switch-on time cooling
tOff
Switch-off time cooling
Dew point
Dew point monitoring option
Sensor
Sensor input selection
Correction
Correction value
Emerg. shutd.
Emergency shutdown option
Humidity
Relative humidity
Hysteresis
Re-energise hysteresis
Output
Output selection
Backup cooling Backup cooling option
Backup cooling Backup cooling submenu
Mode
Backup cooling mode selection
Output
Output selection
Sensor 1
Allocation reference sensor 1
Allocation reference sensor 2
Sensor 2
(When mode = Zone)
Switch-on temperature difference
DTOn
Switch-off temperature difference
DTOff
TOn
Switch-on temperature
TOff
Switch-off temperature
Boiler loading pump output selec-
Loading pump
tion
Start. opt.
Starting optimisation option
Time
Starting optimisation time
Stopp. opt.
Stopping optimisation option
Time
Stopping optimisation time
Holiday
Heating circuit in correction mode
when holiday function is active
Energy saving
Energy saving operation option
Energy saving
Energy saving operation submenu
Sen. return
HC return sensor allocation
Switch-off temperature difference
DTOff
energy saving operation
Break
Break time energy saving operation 0 ... 60 min
Runtime
Runtime energy saving operation
Funct.
De/activation of the heating circuit Activated, Deactivat-
Sensor
Switch input selection
Adjustment range
Factory setting
/ selection
5 ... 29 °C
10 °C
15 ... 45 °C
20 °C
5 ... 25 °C
20 °C
15 ... 45 °C
40 °C
5 ... 25 °C
10 °C
5 ... 29 °C
10 °C
6 ... 30 °C
25 °C
system dependent
system dependent
Outdoor, Ext. Switch,
-
both
-
-
Yes, No
No
20 ... 40 °C
20 °C
Yes, No
No
00:00 ... 23:45
00:00
00:00 ... 23:45
00:00
Humidity, Switch, Off
Off
system dependent
system dependent
0 ... 10 K
2 K
Yes, No
No
5 ... 100 %
95 %
1 ... 10 %
5 %
system dependent
system dependent
Yes, No
No
-
-
Absolute, Therm.,
Absolute
Zone, On/Off
system depend-
system dependent
ent
system depend-
system dependent
ent
system depend-
system dependent
ent
-44,5 ... +15,0 K
-2,0 K
-45,0 ... +14,5 K
-7,0 K
-13 ... +44 °C
+12 °C
-14 ... +43 °C
+8 °C
system depend-
system dependent
ent
Yes, No
No
0 ... 300 min
60 min
Yes, No
No
0 ... 300 min
60 min
Yes, No
No
Yes, No
No
-
-
system dependent
system dependent
1 ... 49 K
4 K
15 min
0 ... 60 min
2 min
Activated
ed, Switch
-
-