Application and function of the
Wilo Net interface
Wilo Net setting
Wilo Net termination
Wilo Net address
Fig. 80: Wilo Net menu setting
Wilo Net termination
Switched off
Switched on
Fig. 81: Wilo Net termination menu
186
NOTICE
After selecting one of the external sources, the setpoint is coupled to this
external source and can no longer be adjusted in the setpoint editor or in
the Home screen.
This coupling can only be cancelled in the menu "Setting the setpoint
source" [" 163]. The setpoint source must be adjusted again to "Internal
setpoint".
The coupling between external source and setpoint is marked both in the
home screen, and in the setpoint editor in blue. The status LED also
becomes blue.
Wilo Net is a bus system that Wilo products (participants) can use to communicate with
each other.
Application for:
twin-head pumps consisting of two participants
Bus topology:
The bus topology consists of several pumps (participants) connected in series. The parti-
cipants are connected via a shared cable.
The bus must be terminated at both ends of the cable. This is done for the two external
pumps in the pump menu. All other subscribers should not have activated termination.
All bus subscribers must be assigned an individual address (Wilo Net ID).
This address is set in the pump menu of the respective pump.
To schedule the pumps, select the following:
Universal
1.0
1.3
1.3.5
1.3.5.1
Possible selection:
Wilo Net termination
Switched off
Switched on
After the termination has been changed, an individual Wilo Net address is assigned to the
pumps.
To assign the Wilo Net address, select the following:
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Display text
Settings
External interfaces
Wilo Net setting
Wilo Net termination
Description
The pump's terminating resistor is switched
off.
If the pump is NOT connected at the end of
the electrical bus line, "Switched off" must
be selected.
Terminating resistor of the pump is switched
on.
If the pump is connected at the end of the
electrical bus line, "Switched on" must be
selected.