Twin-head pump behaviour

11.3
Settings menu - dual pump man-
agement
166
The SSM function must preferably be connected to the main pump. The SSM contact
can be configured as follows:
the contact reacts either only in the event of a fault or in the event of a fault and a
warning.
Factory setting SSM only reacts in the event of a fault.
Alternatively or additionally, the SSM function can also be activated on the standby
pump. Both contacts work in parallel.
ESM: The ESM function of the twin-head pump can be configured on each head of
the twin-head pump head as follows: The ESM function on the SSM contact only sig-
nals faults of the respective pump (individual fault signal). In order to record all faults
of the two pumps, both contacts must be assigned.
SBM/EBM (collective run signal/individual run signal):
The SBM contact can be assigned to any of the two pumps. The following configura-
tion is possible:
The contact is activated when the motor is in operation, power supply is present or
no fault is present.
Factory setting: ready for operation. Both contacts signal the operating status of the
twin-head pump in parallel (collective run signal).
EBM: The EBM function of the twin-head pump can be configured as follows:
The SBM contacts only signal run signals of the respective pump (individual run sig-
nal). In order to record run signals of both the pumps, both contacts must be as-
signed.
Communication between pumps:
Communication for a twin-head pump has been set at the factory.
Wilo Net must be installed with cable between the pumps when connecting two single
pumps of the same type to a twin-head pump.
Then set the termination as well as the Wilo Net address in the menu under "Settings/
external interfaces/Wilo Net setting". Then, in the "Dual pump management" submenu
of the "Settings" menu, select the settings "Connect twin-head pump".
NOTICE
For the installation of two single pumps to form a twin-head pump, see
sections "Twin-head pump installation/Y-pipe installation" [" 139],
"Electrical connection" [" 140] and "Application and function of the Wilo
Net interface" [" 186].
The control of both pumps starts from the main pump to which the differential pressure
sensor is connected.
In case of breakdown/fault/communication interruption, the main pump alone takes over
complete operation. The main pump runs as a single pump according to the set operating
modes of the twin-head pump.
The standby pump, which receives no data from the differential pressure sensor in the con-
trol modes (Δp-v, Δp-c), runs in the following cases at an adjustable constant emergency
operation speed:
The main pump to which the differential pressure sensor is connected fails.
The communication between the main pump and the standby pump is interrupted.
The standby pump starts immediately after detecting a fault.
With the n-const. control mode, there is no adjustable emergency operation. In this case,
the standby pump runs at the last known speed both in main/standby operation and in par-
allel operation.
In the "Dual Pump Management" menu, a twin-head pump connection can be established
or disconnected and you can also set the twin-head pump function.
The
settings menu "Dual Pump Management" has different submenus depending on
the status of the twin-head pump connection.
The following table gives an overview of possible settings in the dual pump management:
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03