Scope of delivery

5.4

Accessories

6

Description of the pump

Fig. 3: View Atmos GIGA-I
Fig. 4: View Atmos GIGA-D
Installation and operating instructions • Wilo-Atmos GIGA-I/-D/-B • Ed.01/2023-06
When using water-glycol mixtures, the use of an S1 variant with a corresponding mech-
anical seal is generally recommended.
The compatibility of the standard seal/standard mechanical seal with the fluid is gener-
ally given under normal system conditions.
Special circumstances may require special seals, for example:
solids, oils or EPDM-attacking substances in the fluid,
air content in the system, etc.
Observe the safety data sheet for the fluid to be pumped!
Pump
Installation and operating instructions
Accessories must be ordered separately:
Atmos GIGA-I/-D/-B:
PTC thermistor tripping unit for switch cabinet installation
Atmos GIGA-I/-D:
3 mounting brackets with fixation material for installation on a base
Atmos GIGA-D:
Blind flanges for repair work
Atmos GIGA-B:
Supports for installation on a base or baseplate for rated powers of 5.5 kW and higher
For a detailed list, consult the catalogue and spare parts documentation.
All the pumps described here are low-pressure centrifugal pumps in compact construction
design with a coupled motor. The mechanical seal is maintenance-free. The pumps can be
installed both directly as a pipe installation pump in a sufficiently anchored pipe or placed
on a foundation base.
The installation options depend on the pump size. Suitable Wilo control devices (e.g. Wilo-
CC-HVAC system) can control the power of the pumps continuously. This allows optimisa-
tion of the pump output for the demands of the installation and economically efficient
pump operation.
Version Atmos GIGA-I
The pump housing has an in-line design, i.e. the flanges on the suction and discharge sides
lie along a centre line. All pump housings are provided with pump support feet. Installation
on a foundation base is recommended for rated powers of 5.5 kW and higher.
Version Atmos GIGA-D
Two pumps are arranged in a shared housing (twin-head pump). The pump housing has an
in-line design. All pump housings are provided with pump support feet. Installation on a
foundation base is recommended for rated powers of 4 kW and higher.
Only the base-load pump is operated in control mode in connection with a control device.
The second pump is available to fulfil full load operation requirements as an auxiliary peak
load. The second pump can adopt the reserve function in the event of a fault.
NOTICE
Blind flanges (accessories) are available for all pump types/housing sizes of
the Atmos GIGA-D series. When replacing the motor impeller unit (motor
with impeller and terminal box), a drive can therefore remain in operation.
NOTICE
To ensure the standby pump is ready for operation, operate the standby
pump every 24 h at least once a week.
en
51