Preparation
Installation and operating instructions Wilo-Yonos PICO OEM

6 Installation and electrical connection

6.1
Installation
May only be installed by qualified technicians.
WARNING!
Risk of burns due to hot surfaces!
Pump housing (1) and glandless pump motor (2) may
become hot and result in burns on contact.
• During operation, touch the control module (6) only.
• Allow the pump to cool down before commencing
any work.
WARNING!
Risk of burns due to hot fluids!
Hot fluids can result in scalding. Before installing or
removing the pump, or undoing the housing screws (5),
note the following:
• Allow the heating system to cool down completely.
• Close shut-off devices or drain the heating system.
• Choose an installation point that is as easily accessible
as possible.
• Observe the pump's allowable installation
position (Fig. 2), rotate the motor head (2 + 6) if
necessary.
CAUTION!
An incorrect installation position may damage the pump.
• Select the installation point in line with the allowable
installation position (Fig. 2).
• The motor must always be installed horizontally.
• The electrical connection must never face upwards.