Herunterladen Inhalt Inhalt Diese Seite drucken

REMS Multi-Push SLW Betriebsanleitung Seite 21

Vorschau ausblenden Andere Handbücher für Multi-Push SLW:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
eng
Fit the REMS fine filter (12) (Art. No. 115609) with filter cartridge 90 µm after 
the house connection (water meter). Connect the suction/pressure hose (13)
to the pressure test with water supply (Fig. 1 (24)) after the fine filter. Connect 
the high-pressure hose (26) to the pressure test with water drain (Fig. 4 (25))
and connect to the installation to be tested. Feed the pressure relief water drain
(27) into a vessel (bucket).
2.7. Cleaning and preservation of heating systems
Before cleaning and preserving heating systems with REMS Multi-Push, safety
devices for the prevention of drinking water contamination by flowback, e.g. 
pipe network separator BA in accordance with EN 1717:2000 must be installed
to protect the drinking water against contamination.
Then fit the REMS fine filter (Fig. 3 (12)) (Art. No. 115609) with filter cartridge 
90 µm. Connect the suction/pressure hose (Fig. 1 (13)) to the flushing supply 
(14) after the fine filter. Fit the REMS V-Jet H (Fig. 7) cleaning and preservation
unit for heating systems with supply (Fig. 7 (16)) to the flushing drain of REMS 
Multi-Push (Fig. 4 (15)). Observe the direction of flow arrows. The main line of 
the cleaning and preservation unit consists of the supply, pressure limiting valve
(17), non-return valve (18), drain to the heating system (19). This is connected
to the heating system to be cleaned by the suction/pressure hose (Fig. 4 (13)).
Part of the supply is pushed through the flow head (Fig. 7 (20)) into the bottle 
(21) which contains the cleaner or corrosion protection for heating systems.
These are fed into the heating system to be cleaned or protected against
corrosion.
NOTICE
Never allow cleaner or corrosion protection agent to flow though the pipes of 
REMS Multi-Push.
Do not use suction/pressure hoses for drinking water lines any more after they
have been used for heating systems.
2.8. Compressed air pump program
Vessels of all types can be pumped up with this program. Connect the compressed
air hose (23) to the output Pressure test with compressed air, Disinfection,
Cleaning, Preservation, Compressed air pump (Fig. 4 (22)) and connect it to
the vessel to be pumped up, e.g. expansion vessel, tyre. The default is displayed
as 0.02 MPa/0, 2 bar/3 psi.
2.9. Memory Manager program (data transfer)
The results of the flushing and test programs are saved with date, time and log 
number in the selected language and can be transferred to a USB stick or
printer (accessory part no. 115604) (neither of which is included in the scope
of supply) for documentation (see 3.6).
2.10. Compressed air tools connection
Unlike the described "Compressed Air Pump" program in which the values are
controlled by the electronic control, compressed air tools up to a max. air
requirement of 230 Nl/min can be operated directly from the compressed air
vessel at the compressed air tools connection (Fig. 4 (28)). A compressed air
hose with quick couplings NW 7.2 must be used (available as an accessory).
3. Operation
NOTICE
REMS Multi-Push is not intended/suitable for permanent connection to the
installation. Disconnect all hoses from the installation after completing the work.
REMS Multi-Push may not be operated unattended.
Before using the REMS Multi-Push, check whether the respective latest version
software is installed on the input and control unit. Select the Settings menu and
then Device data to display the version software. The latest version software
(Ver. Software) for the input and control unit is available by USB stick as a
download: www.rems.de → Downloads → Software → REMS Multi-Push → 
Download. Compare the number of the version software of the unit with the
latest version software number and install the latest version software if neces-
sary.
Download procedure:
1.  Download file
2.  Unpack the ZIP file
3. Save "update.bin" on USB stick
4. Plug the USB stick into the USB port of the REMS Multi-Push
See 2.3 for the further procedure.
NOTICE
The defaults for the different test criteria (test sequences, pressures and times)
in the settings menu of the REMS Multi-Push are taken from EN 806-4:2010
or the information leaflet "Leak tests of drinking water installations with
compressed air, inert gas or water" (January 2011) of the German Central
Association for Sanitary, Heating and Air Conditioning (ZVSHK). All defaults
for the test programs can be edited by the user in the Settings menu and in the
Flushing, Test with compressed air, Test with water and Compressed Air Pump
programs. Changes in the Settings menu are saved, i.e. they reappear the next
time the REMS Multi-Push is switched on. If the defaults are only changed in
one of the programs, the original defaults appear again the next time the REMS
Multi-Push is switched on. Reset resets all defaults to factory settings and the
language to German (deu) and the date, time, units formats to DD.MM.YYYY,
24 h, m / bar.
Attention: The user is solely responsible for transferred or newly entered
test criteria (test sequences, pressures and times) or defaults in the
individual programs and the conclusions from the tests. Especially, the
user must decide whether a prescribed stabilisation/wit time is ended
and must confirm this by \Enter.
The respective national safety provisions, rules and regulations valid for
the application site must be considered and observed.
The electronic memory of REMS Multi-Push holds 40 files (logs). A soon as a 
program has been selected from the Start menu and the selected data have
been confirmed with Enter, a new file no. is created automatically even if the 
program is then abortede.g. with Esc. If the 40th memory location is occupied,
the message "Last file no. available". After completing this process, all files 
should be copied to a USB stick via the USB port (Fig. 2 (33)). The oldest file 
no. in the memory is then overwritten when further files are saved. 
Screen display (must be released by Enter):
000425
Consecutive file no. 000425
19.08.2013 10:13
Date 19.08.2013    Time 10:13 (creation of a new file no.)
Files 40/40
Files 40/40 (a max. of 40 files are saved)
Last file no.
Last file no.
available
available
3.1. Flushing of drinking water installations programs
In EN 806-4:2010 and for Germany additionally in Technical Rules – Worksheet
DVGW W 557 (A) October 2012 of the DVGW German Association of the Gas
and Water Industry e. V. and in the information leaflet "Flushing, disinfection 
and commissioning of drinking water installations" (August 2014) of the German
Central Association for Sanitary, Heating and Air Conditioning (ZVSHK) the
flushing methods "flushing with water" and "Flushing with water/air mixture with 
pressure surges" are described. REMS Multi-Push additionally offers the flushing 
program "flushing with water/air mixture with constant compressed air".
Excerpt from EN 806-4:2010, 6.2.1. "The drinking water installation must be
flushed with drinking water after installation and pressure testing as well as 
immediately before commissioning." "If a system is not put into operation
immediately after commissioning, it must be flushed at regular intervals (up to 
7 days)."
3.1.1. Flushing with water program (without air supply)
In accordance with EN 806-4:2010 and for Germany additionally in accordance
with the Technical Rule – Worksheet DVGW W 557 (A) October 2012 of the
DVGW German Gas and Water Association and the information leaflet "Flushing, 
Disinfection and Commissioning of Drinking Water Installations" (August 2014)
of the Central Association for Sanitary, Heating, Air Conditioning (ZVSHK),
Germany, the drinking water used for flushing must be filtered whereby particles 
≥ 150 µm must be held back and must be suitable for perfect drinking water 
quality (use REMS fine filter and filter cartridge 90 µm, Art. No. 115609). The 
system must be flushed section for section depending on the size of the instal-
lation and the arrangement and lay of the pipes. Flushing must be start on the
bottom floor of the building and continue upwards in lines, within a line floor by 
floor, i.e. from the nearest to the furthest line and floor. The minimum flow 
velocity when flushing the installation must be 2 m/s and the water in the system 
must be replaced at least 20 times during flushing. 
Within the floor and single lines, at least as many tapping points as listed in the 
following table as a recommended value for a flushing section will be fully 
opened for at least 5 minutes floor by floor.
Greatest rated width of the pipe in the
flushed section, DN
Greatest rated width of the pipe in the flushed
section, in inches
Minimum number of tapping points to be
opened DN 15 (½")
Table 1: Recommended value for the minimum number of tapping points to be
opened related to the greatest rated width of the distribution line" (single tapping
rate at least 10l/20 s) (Information leaflet "Flushing, disinfection and commis-
sioning of drinking water installations" (August 2014) of the German Central
Association for Sanitary, Heating and Air Conditioning, lines in italics added,
limiting to DN 50). Two or more REMS Multi-Push can be connected in parallel
to flush greater rated widths.
REMS Multi-Push displays the achieved flow velocity and the achieved water 
change on the screen among other things.
Program sequence ↑ ↓ (8):
1. Flush \ Enter
2. without compressed air \ Enter
3. Check default max. DN according to table 1 and change if necessary
(11) \ ↓
4.  Enter water volume of the flushing section VA H
Fig. 6)
5.  Open the water supply. The values flash as long as the minimum flow 
velocity v H
O = 2 m/s and the water change n H
2
reached. On reaching the values \ Enter
(If the defaults v H
O and n H
2
cause, repeat the process)
25
32
40
1"
1¼"
1½"
2
4
6
O (0-999 l) \ Enter (see
2
O = 20 have not been
2
O are not reached: \ Esc = cancel, clarify the
2
eng
50
2"
8
21

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Multi-push sl

Inhaltsverzeichnis