Fig. 52: Menu 1.01
Fig. 53: Menu 1.04
Fig. 54: Menu 1.07
Fig. 55: Menu 1.08
Fig. 56: Menu 1.09
Fig. 57: Menu 1.10
Fig. 58: Menu 1.11
Installation and operating instructions Wilo-Control EC/ECe-Booster
All manuals and user guides at all-guides.com
Commissioning
Menu 1: Values for switching on and off
Menu no.
Description
Value range
Factory setting
Explanation
Menu no.
Description
Value range
Factory setting
Menu no.
Description
Value range
Factory setting
Menu no.
Description
Value range
Factory setting
Menu no.
Description
Value range
Factory setting
Menu no.
Description
Value range
Factory setting
Menu no.
Description
Value range
Factory setting
1.01
Pressure setpoint
0.1 ... 25.0* bar
4 bar
* The maximum value is dependent on the set measure-
ment range of the pressure sensor (Menu 5.11).
1.04
Activation threshold of the pump in % of the pressure set-
point
75 ... 99 %
95 %
1.07
Base-load pump deactivation threshold in % of pressure
setpoint
101 ... 125 %
115 %
1.08 (Control EC-Booster only)
Peak-load pump deactivation threshold in % of pressure
setpoint
101 ... 125 %
110 %
1.09
Base-load pump switch-off delay
0 ... 180 s
10 s
1.10
Peak-load pump activation delay
0 ... 30 s
3 s
1.11
Peak-load pump switch-off delay
0 ... 30 s
3 s
en
73