12.7
Application and function of the
analogue inputs AI1 and AI2
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Main pump
States
EXT. OFF Behaviour of
the pump
motor
1
Active
Off
2
Not act-
On
ive
3
Active
Off
4
Not act-
On
ive
Table 28: Single mode
Combined mode
The control input DI1 is equipped in the factory with a converter bridge and the function
"EXT. OFF" is active. The control input of the main pump switches both twin-head pump
partners off. The control input of the partner pump only switches the partner pump off. If
the main pump fails or the twin-head pump connection is disconnected, the control input of
the partner pump is evaluated.
Main pump
States
EXT. OFF Behaviour of
the pump
motor
1
Active
Off
2
Not act-
On
ive
3
Active
Off
4
Not act-
On
ive
Table 29: Combined mode
NOTICE
During regular operation, it is preferable to switch the pump on or off via
the DI input with EXT. OFF rather than via the mains voltage!
NOTICE
The 24 V DC power supply is only available when the analogue input AI1 or
AI2 has been configured to a type of use and a signal type or when the di-
gital input DI1 has been configured.
Analogue inputs can be used for setpoint input or actual value input. The assignment of the
target and actual value specifications depends on the selected control mode.
Analogue input AI1 is used as actual value input (sensor value). Analogue input AI2 is used
as setpoint input.
Partner pump
Display text
EXT. OFF Behaviour of
for active
the pump
influences
motor
OFF
Active
Off
Override OFF
(DI1)
OK; normal
Active
Off
operation
OFF
Not act-
On
Override OFF
ive
(DI1)
OK; normal
Not act-
On
operation
ive
Partner pump
Display text
EXT. OFF Behaviour of
for active
the pump
influences
motor
OFF
Active
Off
Override OFF
(DI1)
OK; normal
Active
Off
operation
OFF
Not act-
Off
Override OFF
ive
(DI1)
OK; normal
Not act-
On
operation
ive
en
Display text
for active
influences
OFF
Override OFF
(DI1/2)
OFF
Override OFF
(DI1/2)
OK; normal
operation
OK; normal
operation
Display text
for active
influences
OFF
Override OFF
(DI1)
OFF
Override OFF
(DI1)
OFF
Override OFF
(DI1)
OK; normal
operation