Setpoint source
Internal setpoint
Analogue input (AI2)
CIF module
Fig. 74: Setpoint source menu
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
The actual value of the differential pressure runs between the analogue signals 2 ... 10 V or
4 ... 20 mA. It is linearly interpolated.
The applied analogue signal of 2 V or 4 mA represents the actual value of the differential
pressure at "0 %". The applied analogue signal of 10 V or 20 mA represents the actual value
of the differential pressure at "100 %". (See diagram Fig. 72).
The setpoint to which the pump controls is specified according to "Control settings" section.
The adjustment is made in menu "Control setting" [" 160], "Set setpoint source" [" 163].
"Internal setpoint" must be activated.
Universal
1.0
1.1
1.1.9
1.1.9 / 1
1.1.9 / 2
1.1.9 / 3
The "Cable break detection" function is active.
An analogue signal smaller than 1 V or 2 mA is recognised as a cable break.
Switching on or off takes a hysteresis into account.
A set emergency operation speed is then used as emergency operation. For this, the emer-
gency operation must be set to "Pump ON" in the menu "Control setting – Emergency oper-
ation [" 163]". If the emergency operation is set to "Pump OFF", the pump stops when a
cable break is detected.
Signal type 0 ... 10 V / 0 ... 20 mA
Setting of an on-site differential pressure sensor:
If a differential pressure sensor is set up on-site at analogue input AI1 (for instance at a
pump version R1), the pressure sensor range and the pressure sensor position must be set at
the analogue input AI1 (see Fig. 69) - analogue input AI1. Possible pressure sensor positions:
Pump flange
Standard-compliant position
NOTICE
Recommendation: Set the pressure sensor range to be set at least as high
as the maximum possible delivery head of the respective pump type.
The pressure sensor range must be configured in the "Pressure sensor
range" menu. (Fig. 69 Menu analogue input AI1 and Fig. 71 Pressure sensor
range AI1)
Example:
If the pump type has a maximum delivery head of 20 m, the differential pressure sensor to be
connected must be capable of at least 2.0 bar (approx. 20 m). If a differential pressure sensor
with, for example, 4.0 bar is connected, the differential pressure range must be set to 4.0 bar.
The appropriate signal type for the differential pressure sensor to be connected must always
be selected. In this case 0 ... 10 V or 0 ... 20 mA.
NOTICE
The differential pressure range that is set must always be set to the nom-
inal maximum value of the connected differential pressure sensor. The
nominal maximum value corresponds to the sensor value 100 %. The value
must be read from the rating plate of the differential pressure sensor. This
is the only way to ensure that the pump controls correctly.
The actual value of the differential pressure runs between the analogue signals 0 ... 10 V or
0 ... 20 mA. It is interpolated linearly. (See diagram Fig. 75).
The applied analogue signal of 0 V or 0 mA represents the actual value of the differential
pressure at "0 %". The applied analogue signal of 10 V or 20 mA represents the actual value
of the differential pressure at "100 %".
Display text
Settings
Control settings
Setpoint source
Internal setpoint
Analogue input (AI2)
CIF module
en
183