Dual pump management
Connecting twin-head pump
Pump housing type
Fig. 49: Dual pump management menu
Connecting twin-head pump
Twin-head pump partner
address
Establish twin-head pump
connection
Fig. 50: Connect twin-head pump menu
168
Menu "Connecting twin-head pump"
If a twin-head pump connection has not yet been established, select the following in the
"Settings" menu
:
Universal
1.0
1.4
1.4.1
The Wilo Net address of the twin-head pump partner must first be set for both pumps of the
twin-head pump.
Example:
Pump I is assigned the Wilo Net address 1, pump II the Wilo Net address 2.
The address 2 of the twin-head pump partner must then be set in pump I and address 1 in
pump II.
Connecting twin-head pump
Twin-head pump partner
address
Establish twin-head pump
connection
NOTICE
For notes on the Wilo Net address, see sections "Application and function
of the Wilo Net interface" [" 186] and "Connection of Wilo Net for twin-
head pump function" [" 148].
When the configuration of the partner addresses is complete, the twin-head pump connec-
tion can be started or cancelled.
Universal
1.4.1
1.4.1.1
1.4.1.2
NOTICE
The pump from which the twin-head pump connection is started is the
main pump. Always select the pump to which the differential pressure
sensor is connected as the main pump.
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Display text
Settings
Dual pump management
Connecting twin-head pump
Display text
Connecting twin-head pump
Twin-head pump partner address
Establish twin-head pump connection
Twin-head pump
partner address