External interfaces
SSM relay
SBM relay
Control input
Fig. 58: External interfaces menu
SSM relay
SSM relay function
SSM relay
forced control
Fig. 59: Menu SSM-relay
SSM relay function menu
(activated if ...)
Error present
Error or warning
present
Fig. 60: SSM relay function menu
Twin-head pump
SSM relay function
System mode (SSM)
Single pump mode (ESM)
Fig. 61: Twin-head pump SSM relay function
menu
174
To do this, select the following in the menu:
Universal
1.0
1.3
1.3.1
1.3.1.2
1.3.1.2 / 1
1.3.1.2 / 2
1.3.1.2 / 3
1
Only appears if twin-head pump is configured.
Possible settings:
Selection option
Only fault (factory setting)
Faults and warnings
Table 22: Function SSM relay
SSM/ESM (collective fault signal/individual fault signal) in twin-head pump operation
SSM: The SSM function must preferably be connected to the main pump.
The SSM contact can be configured as follows: the contact reacts either only in the event
of a fault or in the event of a fault and a warning.
Factory setting: SSM only reacts in the event of a fault.
Alternatively or additionally, the SSM function can also be activated on the standby pump.
Both contacts work in parallel.
ESM: The ESM function of the twin-head pump can be configured on each twin-head
pump head as follows:
The ESM function on the SSM contact only signals faults of the respective pump (indi-
vidual fault signal). In order to detect all faults of the two pumps, the contacts must be
assigned in both drives.
Universal
1.0
1.3
1.3.1
2
1.3.1.4
SSM
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Display text
Settings
External interfaces
SSM relay
1
SSM relay function
Error present
Error or warning present
Error present at twin-head pump head
Function SSM relay
SSM relay connects only in case of fault. Fault means:
The pump is not running.
SSM relay connects only in case of fault or a warning.
Display text
Settings
External interfaces
SSM relay
Twin-head pump
2
SSM relay function
System mode (SSM)