Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Code
Warning
553
Electronic module is de-
fective.
Additional information about causes and remedy
The pump is running, but cannot provide full power under the circumstances.
Contact service.
555 /
Implausible sensor value
557
at analogue input AI1 or
AI2.
Additional information about causes and remedy
Incorrect sensor values may lead to substitute operating modes
that ensure functioning of the pump without the required sensor value.
556 /
Cable break at analogue
558
input AI1 or AI2.
Additional information about causes and remedies:
Cable break detection may lead to substitute operating modes that ensure oper-
ation without the required external value.
Twin-head pump:
If W556 appears in the display of the partner pump without a differential pres-
sure sensor connected, always check the twin-head pump connection as well.
W571 may also be activated, however it is not displayed with the same priority
as W556.
The partner pump without a connected differential pressure sensor interprets it-
self as a single pump due to the missing connection to the main pump. In this
case, it recognises the unconnected differential pressure sensor as a cable break.
560
Incomplete software up-
date.
Additional information about causes and remedy:
Software update was not carried out; pump continues to operate with previous
software version.
561 /
Analogue input voltage
562
overloaded (binary or
analogue).
Additional information about causes and remedy:
Binary inputs are impaired. Functions of binary inputs are not available.
1)
564
BMS
setpoint is missing. Sensor source or BMS
Additional information about causes and remedy:
Control functions impaired. A replacement function is active.
565 /
Signal too strong at ana-
566
logue input AI1 or AI2.
Additional information about causes and remedy:
The signal is processed with the maximum value.
Cause
Remedy
Electronic module is
Replace electronic module.
defective.
The configuration and
Check configuration of the
the present signal lead
input and connected sensor.
to an unusable sensor
value.
The configuration and
Check configuration of the
the present signal help
input and connected sensor.
identify the cable
break.
The software update
Software update with new
was not completed.
software bundle is recom-
mended.
Voltage analogue in-
Check the cables and con-
put short-circuited or
sumers connected to the
too heavily loaded.
analogue input power sup-
ply for short circuits.
1)
Check configuration and
is configured incor-
function of BMS
rectly.
Communication has
failed.
The available signal is
Check input signal.
significantly over the
expected maximum.
en
1)
.
203