12.7.1
Using the analogue input AI1 as a
sensor input (actual value)
Analogue input (AI1)
Signal type
Pressure sensor range
Pressure sensor position
Fig. 69: Analogue input AI1 menu
Signal type (AI1)
Fig. 70: Signal types menu
Pressure sensor range (AI1)
16.0 bar
Fig. 71: Setting the pressure sensor range
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
NOTICE
The 24 V DC power supply is only available when the analogue input AI1
or AI2 has been configured for a type of use and a signal type.
The actual value sensor provides the following:
Differential pressure sensor values for differential pressure control
User-defined sensor values for PID control
When setting the control mode, the type of use of analogue input AI1 as an actual value in-
put (see Table 28) is automatically preconfigured.
To set the signal type, select the following in the menu:
Universal
1.0
1.3
1.3.3
1.3.3.1
Possible signal types when selecting the analogue input as actual value input:
Actual value sensor signal types:
0 ... 10 V: Voltage range from 0 ... 10 V for the transmission of measured values.
2 ... 10 V: voltage range of 2 ... 10 V for the transfer of measurement values. A cable break is
detected at a voltage below 1 V.
0 ... 20 mA: Electric current range from 0 ... 20 mA for the transmission of measured values.
4 ... 20 mA: electric current range of 4 ... 20 mA for transfer of measured values. A cable
break is detected if the electric current is less than 2 mA.
For the transfer of analogue signal values to actual values, only the transfer ramp is now
defined. The transmission characteristics are fixed and are as follows:
Signal type 2 ... 10 V / 4 ... 20 mA
Factory setting:
The analogue input AI1 is factory-set with the differential pressure sensor (with variant R1:
not assigned) and set to signal type 2 ... 10 V.
"Pump flange" is set as the pressure sensor position.
The pressure value set in the factory as the pressure sensor range (see Fig. 69 Menu analogue
input AI1 and Fig. 71 Pressure sensor range AI1) corresponds to the maximum sensor range
of the connected differential pressure sensor.
The pressure sensor range varies depending on the pump type.
The sensor range is documented on the rating plate of the differential pressure sensor.
Universal
1.3.3
1.3.3.1
1.3.3.2
1.3.3.3
1.3.3.3 / 1
1.3.3.3 / 2
The actual value of the differential pressure runs linearly between the analogue signals 2 V
and 10 V. This corresponds to 0 % ... 100 % of the sensor measuring range. (See diagram
Fig. 72).
Display text
Settings
External interfaces
Analogue input (AI1)
Signal type
Display text
Analogue input (AI1)
Signal type
Pressure sensor range
Pressure sensor position
Pump flange
Standard-compliant position
en