12.3

SSM relay forced control

SSM relay
forced control
Normal
Forced active
Forced inactive
Fig. 62: SSM relay forced control
12.4

SBM application and function

Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Universal
ESM
2
These sub-menus only appear when the twin-head pump is connected.
An SSM/SBM relay forced control is used as function test of the SSM relay and electrical
connections.
To do this, select the following in the menu:
Universal
1.0
1.3
1.3.1
1.3.1.6
1.3.1.6 / 1
1.3.1.6 / 2
1.3.1.6 / 3
Selection options:
SSM relay
Forced control
Normal
Forced active
Forced inactive
Table 23: Selection option SSM relay forced control
The "Forced active" setting permanently activates the relay. This means that, for example, a
warning note (light) is permanently displayed/announced.
The "Forced inactive" setting leaves the relay permanently without a signal. No warning note
can be confirmed.
The contact of the collective run signal (SBM, potential-free changeover contact) can be
connected to a building automation system. The SBM contact signals the operating status
of the pump.
The SBM contact can be assigned to any of the two pumps. The following configuration
is possible:
The contact is activated when the motor is in operation, power supply is present (net-
work-ready) or no fault is present (ready for operation).
Factory setting: ready for operation. Both contacts signal the operating status of the
twin-head pump in parallel (collective run signal).
Depending on the configuration, the contact is set to NO or NC.
To do this, select the following in the menu:
Display text
Single pump mode (ESM)
Display text
Settings
External interfaces
SSM relay
SSM relay
forced control
Normal
Forced active
Forced inactive
Help text
SSM: Depending on the SSM configuration, fault and
warnings influence the SSM relay switching status.
SSM relay switching status is forced ACTIVE.
CAUTION:
SSM does not display the pump status!
SSM/SBM relay switching status is forced INACTIVE.
CAUTION:
SSM does not display the pump status!