Malfunction
Possible cause
Insufficient power supply for the
device
Air is audibly escap-
Leaks between the valve system
ing
and connected pressure line
Pneumatic connections confused
When setting the
A save process was triggered on
address 0x00, the
the bus coupler before the address
address was not re-
0x00 was set.
set to the standard
address (0x03).
Module produces
Cycle time set to less than 1 ms
cycle error
and more than 42 objects mapped
UL LED flashes red
The electronics supply voltage is
less than the lower tolerance limit
(18 V DC) and greater than
10 V DC.
UL LED illuminated
The electronics supply voltage is
red
less than 10 V DC.
UL LED is off
The electronics supply voltage is
significantly less than 10 V DC.
UA LED flashes red
The actuator voltage is less than
the lower tolerance limit
(21.6 V DC) and greater than UA-
OFF.
UA LED illuminated
The actuator voltage is less than
red
UA-OFF.
IO/DIAG LED flashes
The number of configured output
alternately green/
objects that are mapped to the
red
PDO is smaller than the existing
number of modules
IO/DIAG LED illumi-
Diagnostic message from module
nated red
present
IO/DIAG LED flashes
There is no module connected to
red
the bus coupler.
There is no end plate present.
More than 32 electrical compo-
nents are connected on the valve
side (see
g 12.5.3 Impermissible
configurations).
Over ten modules are connected
in the I/O zone (see
version of the I/O
The module circuit boards are not
plugged together correctly
A module circuit board is defective Exchange the defective module.
The bus coupler is defective.
The new module is not recog-
nized.
S/E LED illuminated
Severe network error present
red
Address assigned twice
For Gen.2 only:
Address range 0 and/or 240-255 is
set
S/E LED flashes red
Connection to master has been
disrupted. Ethernet POWERLINK
communication can no longer
take place.
Cycle time set to less than 1 ms
and more than 42 objects mapped
S/E LED green,
Connection to the network has
flashes quickly
been established, but Ethernet
AVENTICS™ Ethernet POWERLINK | R412018143-BAL-001-AH | English
Remedy
Check LEDs UA and UL on the bus
coupler and the electrical supply
plate and supply the devices with
the correct (adequate) voltage.
Check the pressure line connec-
tions and tighten, if necessary
Properly connect the pneumatics
for the pressure lines
Perform the following four steps:
1. Disconnect the bus coupler
from the voltage and set an
address between 1 and 239
(0x01 and 0xFE).
2. Connect the bus coupler to the
voltage and wait 5 seconds,
then disconnect the voltage
again.
3. Set the address switch to 0x00.
4. Re-connect the bus coupler to
the voltage.
The address should now be set
to the standard address (0x03)
(see section
g 9.2.2 Address
setting with the "Browse and
Config" tool
(Gen.1)).
Increase cycle time to at least 1 ms
or map fewer objects
Check the power supply at plug
X1S.
Configure the correct number of
objects.
Check modules.
Connect a module.
Connect an end plate.
Reduce the number of electrical
components on the valve side to
32.
Reduce the number of modules in
g 12.6 Con-
the I/O zone to ten.
Zone).
Check the plug contacts of all
modules (I/O modules, bus cou-
pler, valve drivers, and end plates).
Exchange the bus coupler
Contact AVENTICS GmbH. The ad-
dress is printed on the back cover.
Check network
Changing the Address
Remove address range. These
ranges are invalid.
Check the connection to the mas-
ter.
Increase cycle time to at least 1 ms
or map fewer objects
Connect the module to an Ether-
net POWERLINK system.
Malfunction
Possible cause
POWERLINK communication has
not yet been established.
L/A 1 or L/A 2 LED il-
No data exchange with the bus
luminated in green
coupler, e.g. because the network
section is not connected to a con-
troller
Bus coupler was not configured in
the controller.
L/A 1 or L/A 2 LED is
There is no connection to a net-
off
work participant.
The bus cable is defective and no
connection can be made with the
next network participant.
Another network participant is de-
fective.
Bus coupler is defective.
See also
2 Impermissible configurations [} 51]
2 Conversion of the I/O Zone [} 52]

14 Key technical data

Table 34: Technical data
General data
Dimensions
Weight
Operating temperature range
Storage temperature range
Ambient operating conditions
Vibration resistance
Shock resistance
Protection class according to EN60529/
IEC60529
Relative humidity
Degree of contamination
Use
Electronics
Electronics power supply
Actuator voltage
Valve inrush current
Rated current for both 24 V power supplies
Connections
BUS
Bus protocol
Connections
Output data quantity
Input data quantity
Standards and directives
DIN EN 61000-6-2 "Electromagnetic compatibility" (Interference immunity for industrial en-
vironments)
DIN EN 61000-6-4 "Electromagnetic compatibility" (Interference emission for industrial en-
vironments)
Remedy
Switch on the Ethernet POWER-
LINK controller.
Connect the network section with
a controller.
Configure bus coupler in the con-
troller.
Connect fieldbus connection X7E1
or X7E2 with a network participant
(e.g. a hub).
Exchange the bus cable.
Exchange network participant.
Exchange the bus coupler
37.5 mm x 52 mm x 102 mm
0.17 kg
-10 °C to 60 °C
-25 °C to 80 °C
Max. height above sea level: 2000 m
Wall mounting EN 60068-2-6:
• ±0.35 mm displacement at 10 Hz to
60 Hz,
• 5 g acceleration at 60 Hz to 150 Hz
Wall mounting EN 60068-2-27:
• 30 g with 18 ms duration,
• 3 shocks each direction
IP65 with assembled connections
95 %, non condensing
2
Only in closed rooms
24 V DC ±25 %
24 V DC ±10 %
50 mA
4 A
Power supply for bus coupler X1S:
• Plug, male, M12, 4-pin, A-coded
Functional earth (FE)
• Connection according to
DIN EN 60204-1/IEC60204-1
Ethernet POWERLINK
Fieldbus connections X7E1 and X7E2:
• Socket, female, M12, 4-pin, D-coded
Max. 512 bits
Max. 512 bits
53