Impermissible, non-compliant expansion!
Any expansions or reductions not described in these instructions interfere with
the basic configuration settings. This will prevent a reliable system configura-
tion.
1. Observe the rules for the expansion of the valve zone.
2. Observe the specifications of the system owner as well as any restrictions
resulting from the overall system.
You may use the following components for the expansion or conversion of the
system:
• Valve driver with base plates
• Pressure regulators with base plates
• Pneumatic supply plates with bridge card
• Electrical supply plates with supply board
• Pneumatic supply plates with UA-OFF monitoring board
With valve drivers, combinations of several of the following components are pos-
sible. See g Fig. 22.
• Valve driver, 4x, with two base plates, 2x
• Valve driver, 3x, with one base plate, 3x
• Valve driver, 2x, with one base plate, 2x
If you would like to operate the valve system as a stand-alone system,
a special right end plate is required (see g 15.1 Accessories).

12.5.1 Sections

The valve zone of a valve system can consist of multiple sections. A section al-
ways starts with a supply plate that marks the beginning of a new pressure or
voltage zone.
An UA-OFF monitoring board should only be installed after an electri-
cal supply plate, otherwise the actuator voltage UA is monitored be-
fore supply.
43
28 29
20 24 22 23 30 44
30
UA
P
S1
Fig. 22: Creating sections with two pneumatic supply plates and one electrical
supply plate
28
Bus coupler
30
Pneumatic supply plate
20
Base plate, 2x
24
Valve driver board, 4x
23
Valve driver board, 3x
42
Valve position for pressure regulator
35
Electrical supply plate
61
Valve
S2
Section 2
P
Pressure supply
UA
Power supply
The valve system consists of three sections. See g Fig. 22.
Table 31: Example valve system, consisting of three sections
Section
Components
Section 1
• Pneumatic supply plate (30)
• Three base plates, 2x (20), and one base plate, 3x (21)
• Valve driver boards, 4x (24), 2x (22), and 3x (23)
• 9 valves (61)
AVENTICS™ Ethernet POWERLINK | R412018143-BAL-001-AH | English
NOTICE
42 41
35 38 61
P
UA
A
S2
S3
29
Transition plate
43
Long bridge card
21
Base plate, 3x
22
Valve driver board, 2x
44
Short bridge card
41
Integrated AV-EP circuit board
38
Supply board
S1
Section 1
S3
Section 3
A
Single pressure control working con-
nection
Section
Components
Section 2
• Pneumatic supply plate (30)
• Four base plates, 2x (20)
• Two valve driver boards, 4x (24)
• 8 valves (61)
• AV-EP base plate, single pressure control
• AV-EP pressure regulator
Section 3
• Electrical supply plate (35)
• Two base plates, 2x (20), and one base plate, 3x (21)
• Supply board (38), valve driver board, 4x (24), and valve driver board, 3x
(23)
• 7 valves (61)

12.5.2 Permissible configurations

AES-
D-BC-
PWL
UA
P
A
B
B
Fig. 23: Permissible configurations
You can expand the valve system at all points designated with an arrow:
• After a pneumatic supply plate (A)
• After a valve driver board (B)
• At the end of a section (C)
• At the end of the valve system (D)
To simplify your documentation and configuration, we recommend
that you expand the valve system on the right end (D).

12.5.3 Impermissible configurations

The following figure displays the configurations that are not permissible. See
g Fig. 24.
You may not:
• Split a 4x or 3x valve driver board (A)
• Mount fewer than four valve positions after the bus coupler (B)
• Mount more than 64 valves (128 solenoid coils)
• Integrate more than 8 AV-EPs
• Integrate more than 32 electrical components
Some configured components have multiple functions and therefore count as
multiple electrical components.
Table 32: Number of electrical components per component
Configured component
Valve driver boards, 2x
Valve driver boards, 3x
Valve driver boards, 4x
Pressure regulators
Electrical supply plate
UA-OFF monitoring board
P
UA
C A
B
C
B
Number of electrical components
1
1
1
3
1
1
D