Once you have entered the desired settings, click on "Write to Device".
u
If the "Properties successfully changed" message appears, the settings were
saved.
If an error message appears:
Check the entries you made and try to write them to the device again.
u
If an error message appears again:
Reset the bus coupler power and repeat the procedure from step 7.
u
AVENTICS™ Ethernet POWERLINK | R412018143-BAL-001-AH | English
We recommend noting the bus coupler MAC address together with
the set address. You will be able to use the MAC address to determine
which address is set in the bus coupler during installation. Alterna-
tively, you can note the set address on the bus coupler, e.g. on the la-
bels for the equipment ID.
10 Commissioning the Valve System with Ethernet
POWERLINK
Before commissioning the system, the following steps must have been carried
out and completed:
• You have assembled the valve system with bus coupler (see the assembly in-
structions for the bus couplers and I/O modules, as well as the valve system).
• You have carried out the presettings and configuration (see
on the Bus Coupler
and
g 5. PLC Configuration of the AV Valve
• You have connected the bus coupler to the controller (see AV valve system as-
sembly instructions).
• You have configured the controller so that it actuates the valves and the I/
O modules correctly.
Commissioning and operation may only be carried out by qualified
electrical or pneumatic personnel or an instructed person under the di-
rection and supervision of qualified personnel (see
qualifications).
Danger of explosion with no impact protection!
Mechanical damage, e.g. strain on the pneumatic or electrical connectors, will
lead to non-compliance with the IP65 protection class.
In explosive environments, make sure that the equipment is installed in a
u
manner that protects it from all types of mechanical damage.
Danger of explosion due to damaged housings!
Damaged housings can lead to an explosion in explosive areas.
Make sure that the valve system components are only operated with com-
u
pletely assembled and intact housing.
Danger of explosion due to missing seals and plugs!
Liquids and foreign objects could penetrate and destroy the device.
1. Make sure that the seals are integrated in the connections and not dam-
aged.
2. Make sure that all connections are mounted before starting the system.
Risk of uncontrolled movements when switching on the system!
There is a danger of personal injury if the system is in an undefined state.
1. Put the system in a safe state before switching it on.
2. Make sure that no personnel are within the hazardous zone when the com-
pressed air supply is switched on.
1. Switch on the operating voltage.
The controller sends parameters and configuration data to the bus coupler,
electronic components in the valve zone, and I/O modules during startup.
2. After the initialization phase, check the LED statuses on all modules (see
g 11. LED Diagnosis on the Bus Coupler
modules).
Before applying the operating pressure, the diagnostic LEDs may only be illumi-
nated in green. See g Table 23.