Herunterladen Inhalt Inhalt Diese Seite drucken

Aventics HF03 Betriebsanleitung Seite 73

Vorschau ausblenden Andere Handbücher für HF03:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
AVENTICS | HF03/HF02 | 1987765493–BDL–001–AB
Observe the following points during installation:
O
Turn off the system operating voltage and compressed
air.
O
A maximum of 12 input/output modules can be mounted
on one VS. Observe the current load!
O
The input modules should preferentially be mounted on
the bus coupler for EMC reasons.
O
The maximum number of input/output modules that are
lined up directly on the left of the bus coupler depends on
the maximum permissible current load on P24VN from
POWER X10 on the bus coupler for inputs and outputs.
O
The maximum number of input/output modules that are
lined up directly on the left of the power module depends
on the maximum permissible current load on P24VN
form POWER X10 on the power module for outputs.
1. Remove the left side cover from the last valve system
I/O module (3 hexagon socket head screws, DIN 912 M4,
wrench width 3)
2. Depending on the position in which the power module should
be installed and depending on the order the input/output
modules should be placed, the appropriate input/output
modules should be removed. (3 hexagon socket head screws
each, DIN 912 M4, wrench width 3)
3. Line up the input modules preferably on the bus coupler and
screw them tight (3 hexagon socket head screws, DIN 912 M4,
wrench width 3).
Tightening torque: 2.5 ... 3.0 Nm
4. Add the power module and screw it tight (3 hexagon socket
head screws, DIN 912 M4, wrench width 3).
Tightening torque: 2.5 ... 3.0 Nm
5. Line up the rest of the input/output modules on the power
module and screw them tight (3 hexagon socket head
screws each, DIN 912 M4, wrench width 3).
Tightening torque: 2.5 ... 3.0 Nm
Conversion and extension