AVENTICS | HF03/HF02 | 1987765493–BDL–001–AB
Installation
Power consumption
Assembling the
connection plug
See Fig. 4/5 and Fig. 8
Current too high in GND (0 V) wire
A current of over 4 A in the 0 V line may damage the product
or system parts
O
If possible, externally connect the 0 V loads; this is
mandatory from 4 A total current.
Table 16:
32 I/O box power consumption
Signal
Assignment
P24VO1
Load supply, X1 and X2
P24VO2
Load supply, X3 and X4
P24VO3
Load supply, X5 and X6
P24VO4
Load supply, X7 and X8
P24VI
Sensor and logic supply
Through the separate load supply of bytes 1-4 (P24VO1-
P24VO4) it is possible to, for example, permanently connect
bytes 1-3 via the emergency off and byte 4 to 24 V DC.
1. For easy access to the internal plug, choose a suitable place
(threaded for PG 13.5) for introducing the cable.
2. Be aware of the plug sequence inside the 32 I/O box, so that
all plugs can be reached.
3. Connect the supplied bushings (screw connection) and plug
them into the appropriate plugs.
4. Choose a suitable grommet for the cable feed-through,
individual wires, as well as multi-conductor cable with
various diameters.
5. After fastening the cable feed-through, insert the cable
and secure it.
NOTICE
Current
Max. 4.0 A
Max. 4.0 A
Max. 4.0 A
Max. 4.0 A
Max. 2.3 A