POWER X10
plug assignment
(power module)
POWER X10
power consumption
(power module)
AVENTICS | HF03/HF02 | 1987765493–BDL–001–AB
There is an internal connection between the PGND pin on
X10 and the PGND pin on the bus coupler's X10 if a power
module is present.
That means: if a power supply unit without safe isolation
is used and the power supply is only connected to one of the
two X10 plugs, voltage can form on the PGND pin which
is dangerous when touched!
O
The 24 V power supply must stem from a power supply
unit pack which is electrically isolated according to
DIN EN 60742, classification VDE 0551.
Table 8:
POWER X10 plug assignment (power module)
Pin
POWER X10
1
PG
2
P24VN
3
PGND
4
5
6
There is an internal connection between the PGND pin on
X10 and the PGND pin on the bus coupler's X10 if a power
module is present.
The power consumption should be set accordingly. When
choosing suitable cable cross-sections, the cable length and the
emitted currents should be considered:
Table 9:
POWER X10 power consumption (power module)
Signal
Assignment
P24VN
Outputs
CAUTION
Assignment
Protective ground (protruding contact)
Output voltage supply
Ground for P24VN
Not connected
Not connected
Not connected
Total current
Max. 12 A