Abschnitt 5
Stationskommunikation
700
Function block with defined IED functions in monitor direction, I103IED. This
block use PARAMETER as FUNCTION TYPE, and INFORMATION NUMBER
parameter is defined for each input signal.
Function status indication in monitor direction, user-defined
Function blocks with user defined input signals in monitor direction, I103UserDef.
These function blocks include the FUNCTION TYPE parameter for each block in
the private range, and the INFORMATION NUMBER parameter for each input
signal.
Supervision indications in monitor direction
Function block with defined functions for supervision indications in monitor
direction, I103Superv. This block includes the FUNCTION TYPE parameter, and
the INFORMATION NUMBER parameter is defined for each output signal.
Earth fault indications in monitor direction
Function block with defined functions for earth fault indications in monitor
direction, I103EF. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Fault indications in monitor direction, type 1
Function block with defined functions for fault indications in monitor direction,
I103FltDis. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal. This block
is suitable for distance protection function.
Fault indications in monitor direction, type 2
Function block with defined functions for fault indications in monitor direction,
I103FltStd. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal.
This block is suitable for line differential, transformer differential, over-current and
earth-fault protection functions.
Autorecloser indications in monitor direction
Function block with defined functions for autorecloser indications in monitor
direction, I103AR. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Messwerte
Die Messwerte können gemäß der Norm als Typ 3.1, 3.2, 3.3, 3.4 und Typ 9
verwendet werden.
1MRK 505 186-UDE B
Applikationshandbuch