10 Technical Data
Long term stability
Accuracy of reference
junction
Installation hints
Ambient temperature
Storage temperature
Condensation
Ingress protection
Electromagnetic
compatibility (EMC)
108
mV (-50 to 500 mV):
±0.03% of FSD or 0.05 mV, the highest value is valid.
Ohm (0 to 100), RTD (GE: Cu10):
±0.03% of FSD or 0.01, the highest value is valid.
Ohm (0 to 400), RTD (DIN: Ni120; IEC: Pt50, Pt100; JIS: Pt50, Pt100):
±0.03% of FSD or 0.04, the highest value is valid.
Ohm (0 to 2000), RTD (IEC: Pt500):
±0.03% of FSD or 0.2, the highest value is valid.
RTD: ≤ 0.1K/24 months
1
TC: ≤ 0.1K/12 months
1
±0.25 °C (internal reference junction on thermocouples TC)
10.6 Application conditions (installation conditions)
• Installation angle:
No limitations
10.7 Application conditions (ambient conditions)
Without display: -40 to +85 °C (-40 to +185 °F) (for hazardous areas see Ex certificate)
With display:-10 to +60 °C (-14 to +140 °F) in operation
+60 to +85 °C (+140 °F to +185 °F) operation without defects,
no display function
Without display: -40 to +120 °C (-40 to +250 °F)
With display:-40 to +85 °C (-40 to +185 °F)
10 to 100% RH
NEMA 4X, IP 67
Interference immunity and emission according to EN 61 326-1
1.
Under reference conditions
FOUNDATION Fieldbus temperature transmitter
or ≤ 0.1%/24 months
or ≤ 0,1%/12 months
Endress+Hauser