3 Transport and temporary storage

The pump set is supplied on a wooden pallet. Pro -
tect it from bad weather conditions during trans -
port and storage even if it is protected from
moisture and dust by a plastic bag.
Transport and unload the equipment by author -
ized persons and load devices.
The equipment must be stored indoors and for
maximum six months with proper covering. After
this period, especially for Diesel motor models, the
equipment must be retested.
(See example on Fig.1, 1a, 1b)
Before operation, observe the specific instruc -
tions in the operating manuals of the load/unload
devices.
WARNING! Risk of personal injury!
Consider the static stability of the unit. Quali -
fied personnel must carry out the handling of
the material, using only suitable and authorized
equipment.
Lifting straps must be fastened to the ring bolts
placed on the base frame.
The pump or the motor do not fit with the han -
dling of the system and must not be used to fix
loads in transit.
CAUTION! Risk of product damages!
Handling by using discharge manifold can cause
leakages!
When the product is delivered, check it for any
damage in transit. In case of damage, take any
necessary measures from the delivery company
(forwarding agent).
CAUTION! Risk of product damages!
If the product shall be installed later on, store it
in a dry place. Protect it from impacts and any
outside influences (moisture, frost, and so on...).
Handle the product with care.

3.1 Residual risk during transport and storage

WARNING! Risk of cuts!
Sharp edges or any unprotected threaded parts
entail the risk of being cut.
Take necessary cautions to avoid injuries and
use protective equipment (wear specific
gloves).
WARNING! Risk of personal injury!
Installation and operating instructions Wilo-FireSet UL FM
Do not stand or put members under the sus -
pended parts during handling and installation.
Use clothing dedicated to protection against
accidents (wear helmet and safety shoes).
WARNING! Risk of impact!
Be careful of prominent parts and parts at head
level. Use clothing dedicated to protection
against accidents.
DANGER! Risk of fall!
Prohibit access to the technical room, where
pumps are installed.
WARNING! Risk of irritation!
During handling, avoid spillage of battery acid
solution, which could cause irritations or mate -
rial damage. Use special protection to avoid
contact.
CAUTION! Risk of environmental pollution!
Avoid oil leakage from the motor or diesel fuel
from the tank. During handling, keep them flat.
Use suitable protection and take necessary
measures to prevent pollution of oil, water, etc.

4 Intended use

The fire-extinguishing system is designed for
fixed installation and professional use. It is used
when an increase or maintaining under pressure of
the fire-extinguishing system is necessary.
The fire-extinguishing system must be installed in
a special room, which is protected from frost and
rain, fireproof and sufficiently ventilated, with
enough space provided around the pumps for
maintenance work. The room must be in accord -
ance with the NFPA20 requirements. Airflow for
ventilation and for the cooling of motors, more
specifically the diesel motor - if present - must be
sufficient.

5 Product data

5.1 Type key

Example:
Wilo-FireSet- 125-360-300/137D
Wilo-FireSet
Name of the series
• FireSet-: Name of the fire-extinguishing system
assembled according to NFPA20
• 125-360 Type of the pump Wilo SCPFF UL listed -
FM-approved
• 300: Nominal impeller diameter [mm] - Actual
diameter: Refer to the rating plate
• 137 Nominal power of the drive [kW]
• E - D: Drive
• E: Electric motor
• D: Diesel motor
English