10.3.13.2 Metering monitoring / Stop pump
10.3.13.3 Metering monitoring / Strokes
10.3.13.4 Metering monitoring / Deviation (only at E60
A tolerance in % is set under "deviation".
The actual incoming pulse rate recorded by the oval gear meter within the pump interval to
be monitored (see chapter
target pulse rate defined during calibration.
If this comparison results in a deviation that is greater than the % value configured under
"deviation", a "metering monitoring alarm" is triggered.
This function can only be selected if a dongle plate is connected and configuration/oval gear
NOTE
meter (see chapter
(only E60
417101799_EMP_IV_E60.docx
10.3.13.3
"Metering monitoring/strokes") is compared with the
10.3.11
„ Configuration / Oval gear meter
PLUS
& OGM or OGM
PLUS
)
Fig. 10.35 Configuration / Metering monitoring / Stop pump
The "stop pump" function is used
to set whether or not the pump
should be stopped if a "metering
monitoring alarm" is triggered.
- Pump is not stopped
when a "metering monitoring alarm"
is triggered. (Default setting)
✓ Pump is stopped
when a "metering monitoring alarm"
is triggered.
Fig. 10.36 Configuration / Metering monitoring / Strokes
The "strokes" option indicates the
stroke interval to be monitored.
Setting range: 0 – 100
Default setting = 10
& OGM or OGM
PLUS
"
) has been activated.
Fig. 10.37 Configuration / Metering monitoring / Deviation
Setting range: 0-100%
Default setting = 20 %
- 104 -
)
PLUS
Rev. 11-10.19