Connecting the System
Parameters
BATTERY
VOLT (Battery voltage)
CAPACITY
(Battery capacity)
BMS PARAM (BMS parameters)
TEMP
(Temperature of the
battery)
PV1/PV2 INPUT
VOLT (PV voltage)
GRIDDATA(Grid-connectedOutput)
VOLT (Grid voltage)
Notesonthesystem:
• The recommended ratings of the AC circuit breakers are
ON GRID: 23 A
BACKUP: 25 A
• The method of anti-islanding protection is method (c).
• To manually sleep all battery modules,
it is necessary to disconnect the power line,
communication line and communication line
between battery storage and inverter.
128
Normal range
50V ± 3V
Number of battery modules multiplied by 100AH
Based approximately on the current ambient tem-
perature of the system
Depending on the respective installation situation
Note:
If the PV voltage is 0V even under sunshine,
check the connection direction of the PV cables
and the circuit.
Depending on the respective installation situation