7.3 Error codes, meanings and suggested solutions
Code Fault
F00
Undefined fault
(Soft Time Out)
F01
Short circuit
(INV Volt
Short)
F02
GFCI Sensor
Fault
F04
Low / High
F05
bus voltage
(Bus Volt Low /
High)
F06
Bus voltage
short circuit
(Bus Volt Short
Circuit)
F07
Faulty ground-
ing resistor
(PV ISO Under
Fault)
F08
PV Input Short
Circuit
F09
Relay Fault
F14
(Bypass /
Grid Relay
Fault)
Proposed solutions
• Restart the inverter and wait until it functions normally.
• Disconnect the entire power supply
and shut down all components.
Disconnect the load and plug in to restart the components.
Then check whether the load is short circuited and
if the fault has been eliminated.
• Disconnect the entire power supply,
restart the inverter and wait until it functions normally.
• Check the input mode setting is correct.
• Restart the inverter and wait until it functions normally.
• Restart the inverter and wait until it functions normally.
• Check the grounding.
• Check if the ground resistance of PV+ and PV- is greater
than 2MΩ.
• If it is smaller than 2MΩ, check PV string for ground fault
or poor ground insulation.
• Check the input mode setting is correct.
• Disconnect the PV input,
restart the inverter and wait until it functions normally.
• Have a suitably qualified specialist disconnect
the grid, battery and PV input
and check whether the bypass relay (F9)
or the grid-connected relay (F14) is defective.
• Restart the inverter and wait, until it functions normally.