Reactive response time (REACT RESP)
The time until the reactive power output reaches the grid
standard value is automatically set according to the se-
lected grid standard and should not be changed.
If necessary, set the reactive response time by adjusting
each digit of the input value with the up/down keys  / 
and confirm with the enter key
seconds,
default setting 10 seconds).
To cancel the process and return to the run setting
options, press the escape key .
Bridging function (VRT ENABLE)
This function ensures the continuation of the inverter's
operation in the event of a sudden (short time period)
voltage rise or drop in the grid.
Enable or disable this function by using the up/down
keys  / 
to select the desired one of the two options:
1: Disabling the
high/low voltage ride through capability
2: Enabling the
high/low voltage ride through capability
Use the enter key
or the escape key
to the run setting options.
Power rising rate (POW SI RATE)
During start-up, an increase of the inverter power is
required (100% means that the output will hit full power
within 1 minute).
This setting is automatically adjusted according to
the set grid standard.
The option can be ignored.
(adjustable from 6 to 60
to confirm your selection
to cancel the process and return
Operation and Setting
−REACT RESP−
INPUT:
10 s
−−VRT ENABLE−−
1: DISABLE
2: ENABLE
−POW SI RATE−
INPUT:
100 %
79