Parameter setting of the reactive mode
The reactive power can be monitored in various ways.
This is set automatically according to the selected grid
standard and should not be changed
(if necessary, select options with up/down keys   /   and
confirm or, in the case of 1,2, call up the corresponding
settings menu with the enter key
1: Power factor
2: Reactive power
3: QU wave (Settings reserved for this model)
4: QP wave (Settings reserved for this model)
To cancel the operation and return to the run setting
options, use the escape key .
Setting the selected parameters
After selecting the desired parameter, use the up/down
keys   /   to adjust the corresponding input value
and the enter key
and return to the parameter setting of the reactive mode.
Note: The input values for power factor and reactive power
are automatically set according to the network standard
setting.
Only set them yourself if the network standard required for
the location is not available in the corresponding selection.
Power factor
The input value should be between L 0.80 and L 0.99
or C 0.8 and C 1.00.
Reactive power
The input value should be between -60% and +60%, which
varies according to the standard.
):
to confirm the selection
Operation and Setting
−−REACT MODE−−
1: POWER FACTOR
2: REACT POWER
3: QU CURVE
4: QP CURVE
−POWER FACTOR−
INPUT:
L0.80
−REACT POWER−
INPUT:
L+60%