Operation and Setting
Gridpower (GRIDPERCENT)
Use the up/down keys   /   to adjust the input value
(percentage)
and the enter key
or the escape key
and return to the selection of the run setting options.
voltage and frequency limit values /
protection points for inverter and grid
(VOLT MAX / VOLT MIN / FREQ MAX / FREQ MIN)
The following settings are automatically set according to
the selected network standard and should not be changed
(if necessary, select options with up/down keys   /   ,
confirm, call up the corresponding settings menu with the
enter key
and adjust the input values with the up/down
keys   /   ).
When exceeding or falling below the set values,
power generation is stopped.
Maximum inverter voltage / over voltage protection point
(INV VOLT MAX)
1: Setting the maximum inverter voltage (S1)
(default setting: 280 Vac)
Setting the protection delay time (S1)
(default setting: 1000 ms)
2: Setting the maximum inverter voltage (S2)
(default setting: 285 Vac)
Setting of the protection delay time (S2)
(default setting: 400 ms)
Minimum inverter voltage / low voltage protection point
(INV VOLT MIN)
3: Setting the minimum inverter voltage (S1)
(default setting: 150 Vac)
Setting the protection delay time (S1)
(default setting: 1000 ms)
4: Setting the minimum inverter voltage (S2)
(default setting: 120 Vac)
Setting of the protection delay time (S2)
(default setting: 400 ms)
76
to confirm your entry
to cancel the operation
−GRID PERCENT−
INPUT:
100%
−INV VOLT MAX−
1: VOLT(S1)
2: VOLT(S2)
−INV VOLT MIN−
1: VOLT(S1)
2: VOLT(S2)