Mounting the System
Site restrictions
In the following cases, the specified distances must be observed
when installing the energy storage system:
600 mm to any heat source,
such as hot water unit, gas heater, air conditioning unit
or other similar appliances
600 mm to any exit
600 mm to any window or ventilation opening
900 mm to any access to 240Vac connections
600 mm to any side of another device
1 m clearance when installed in an escape route,
such as a corridor, hallway, lobby or similar
with access to an emergency exit
Installation specifications and distance regulations
• To protect against the spread of fire in living spaces where the H5/
H3 is mounted or on surfaces of a wall or structure in living spaces
with a H5/H3 on the other side, the wall or structure shall have a
suitable non-combustible barrier.
If the mounting surface itself is not made of a suitable non-combus-
tible material, a non-combustible barrier must be placed between
the H5/H3 and the surface of a wall or structure.
• If the H5/H3 is mounted at a wall or at a distance of 300mm from
the wall or the structure separating it from the habitable space, the
distances to other structures or objects must be increased.
The following minimum distances / clearances
around the energy storage system must be observed:
600 mm next to it
500 mm above it
600 mm in front of it
(See also the following sketch)