Maximum inverter frequency /
Inverter over frequency protection point (INV FREQ MAX)
1: Setting the maximum inverter frequency (S1)
(default setting: 55 Hz)
Setting the protection delay time (S1)
(default setting: 500 ms)
2: Setting the maximum inverter frequency (S2)
(default setting: 55 Hz)
Setting the protection delay time (S2)
(default setting: 500 ms)
Minimum inverter frequency /
Inverter low frequency protection point (INV FREQ MIN)
1: Setting the minimum inverter frequency (S1)
(default setting: 45 Hz)
Setting the protection delay time (S1)
(default setting: 500 ms)
2: Setting the minimum inverter frequency (S2)
(default setting: 45 Hz)
Setting the protection delay time (S2)
(default setting: 500 ms)
Maximum grid voltage /
Gridovervoltageprotectionpoint(GRIDUMAX)
(default setting: 280 Vac)
Minimum grid voltage /
Gridlowvoltageprotectionpoint(GRIDUMIN)
(default setting: 130 Vac)
Maximum grid frequency /
Gridoverfrequencyprotectionpoint(GRIDFMAX)
(default setting: 55 Hz)
Minimum grid frequency /
Gridlowfrequencyprotectionpoint(GRIDFMIN)
(default setting: 45 Hz)
To return to the selection of the RUN SETTING,
touch the escape key .
Operation and Setting
−INV FREQ MAX−
1: FREQ(S1)
2: FREQ(S2)
−INV FREQ MIN−
1: FREQ(S1)
2: FREQ(S2)
77